Appendix 1 Specifications - Keatec Energy T 3310E User Manual

T series 10-40kva 380vac 3ph
Table of Contents

Advertisement

Model
Capacity
Rated Voltage
Voltage Range
Frequency Range
Power Factor
Current THDi
Input
Bypass Voltage Range
Generator Input
Rated Voltage
Power Factor
Voltage Regulation
Output
Frequency
Crest Factor
Battery
Charge Current(A)
(charge current can be
set according to battery
capacity installed)
Transfer Time
Protection
Overload
KE 4256-3230 Keatec T Series UPS 10-40K 380Vac Users Guide English 20170126

Appendix 1 Specifications

Phase
Max. voltage: 220Vac: +25%(optional +10%,+15%,+20% )
Min. voltage: -45% (optional -10%, -20%, -30%)
Frequency protection range: ±10%
Phase
Utility
±1%, ±2%, ±4%, ±5%, ±10% of the rated frequency(optional)
Mode
Battery
Mode
THD
E-B UNIT:
±120Vdc (20pcs
12V9AH);
(2x20pcs 12V9AH
Voltage
optional)
E UNIT:
±96V/±108V/±120
Vdc (16/18/20pcs
optional)
E-B UNIT: 1.35A
(2.7A optional)
E UNIT: Max.
current 10A
AC Mode
Bat.
Mode
T 3310E
T3310E-B
10KVA
9KW
3 Phase 4 Wires and Ground
380/400/415Vac
45-55Hz at 50Hz/54-66Hz at 60Hz (auto sensing)
≤3%(100% nonlinear load)
230Vac: +20%(optional +10%,+15% )
240Vac: +15%(optional +10% )
3 Phase 4 Wires and Ground
380/400/415Vac
(50/60±0.2%)Hz
≤2% with linear load
≤5% with non linear load
E-B UNIT: ±120Vdc (2x20pcs 12V9AH);
±96V/±108V/±120Vdc (16/18/20pcs
Utility to Battery : 0ms; Utility to bypass: 0ms
Load≤110%: last 60min,≤125%: last 10min,≤150%: last
1min, >150% change to bypass immediately
Load≤110%: last 10min, ≤125%: last 1min, ≤150%: last
5S, >150% shut down UPS immediately
Page 35
T 3315E
T3315E-B
15KVA
13.5KW
208~478Vac
≥0.99
Support
0.9
±1%
3:1
E UNIT Optional Voltage:
optional)
E-B UNIT: 2.7A
E UNIT: Max. current 10A
This manual is for qualified personnel only.
T 3320E
T3320E-B
20KVA
18KW