Keatec Energy T SERIES User Manual

25 - 100 kva pf 1.0 208 vac with 7.0 touch screen
Hide thumbs Also See for T SERIES:

Advertisement

T SERIES UPS
25 - 100 kVA PF 1.0 208 Vac
with 7.0 Touch Screen
User Guide
UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS
MANUALS OR OTHER DOCUMENTATION;
(B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT,
CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE
ENTIRELY AT THE USER'S RISK; AND
(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE
ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE.
(D) INFORMS YOU THE INFORMATION IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE.
(E) RESERVES ALL RIGHTS.
KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209
This manual is for qualified personnel only

Advertisement

Table of Contents
loading

Summary of Contents for Keatec Energy T SERIES

  • Page 1 (D) INFORMS YOU THE INFORMATION IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. (E) RESERVES ALL RIGHTS. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 2: Table Of Contents

    Appendix 2 USB Communication Port ................ 60 Appendix 3 RS232 Communication Port ..............61 Appendix 4 RS485 Communication Port ..............62 KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 1...
  • Page 3 Appendix 5 Optional Port .................... 63 Appendix 6 REPO Port ....................63 KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 2...
  • Page 4: Safety

    WARNING! A battery can present a risk of electric shock and high short circuit current. The following KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 5: Symbols Used In This Guide

    Risk of Equipment Damage - Refer to the operator’s manual for additional information, such as important operating and maintenance instructions Please recycle batteries appropriately. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 4...
  • Page 6: Main Features

    Integration with Electrical System The UPS can be integrated with external battery cabinet, PDU and external maintenance bypass. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 7: Unpacking And Inspection

    Place the ramp on the ground, use the screws unfastened from the last step to fasten the ramp to the pallet. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 8: Cabinet Overview

    Cabinet Overview 25kVA & 30kVA Front and Side View 25kVA & 30kVA Rear View KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 7...
  • Page 9 (21) Maintenance breaker (22) Bypass breaker (23) Mains breaker (24) Output breaker (25) Terminal block cover KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 8...
  • Page 10 40kVA, 50kVA & 60kVA Front and Side View 40kVA, 50kVA & 60kVA Rear View KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 9...
  • Page 11 (21) Maintenance breaker (22) Bypass breaker (23) Mains breaker (24) Output breaker (25) Terminal block cover KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 10...
  • Page 12 80kVA Front and Side View 80kVA Rear View KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 11...
  • Page 13 (21) Maintenance breaker (22) Bypass breaker (23) Mains breaker (24) Output breaker (25) Terminal block cover KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 12...
  • Page 14 100kVA Front and Side View 100kVA Rear View KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 13...
  • Page 15: Touch Display And Control Panel

    15°C and 25°C. Keep batteries away from heat sources or main air ventilation area, etc. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 16: External Protective Devices

    (or a set of fuses) located close to the battery. UPS Output KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 15...
  • Page 17: Power Cables

    − Routing the cables over the cable ladder or bracket in a single layer (IEC60364-5-52 middle KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 18 100A 3P Mains input circuit breaker 125A 3P 30kVA Bypass input circuit breaker 125A 3P KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 17...
  • Page 19: Power Cable Connections

    Check to see if they are electrically isolated and post any necessary warning signs to prevent their inadvertent operation. • Remove the cover over the terminals. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 18...
  • Page 20 Single Common Input Connection 2.9.1 25kVA & 30kVA 40kVA – 80KVA 100kVA KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 19...
  • Page 21 BAT+: Positive terminal of the battery string BATN: Neutral terminal of the battery string BAT-: Negative terminal of the battery string KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 20...
  • Page 22 Dual Input Connection 2.9.2 25kVA & 30kVA 40kVA – 80kVA 100kVA KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 21...
  • Page 23 Pay attention to the diameter of the connection terminal of the cable, it should be greater than or equal to that of the connection poles. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 24: Battery Connection

    Factory default is battery quantity of 22pcs, battery capacity 12V100AH and charger current 15A. When connecting 16/18/20/24/26pcs batteries, please set the battery quantity and battery capacity KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 25: Parallel Installation

    Make certain the N, A (L1), B (L2), C (L3) lines are correct and grounding is well secured. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 26: Lbs Installation

    The two ports of one mesh wire should be plug into RJ45 interface of any one UPS of both master and slave system. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 27: Installation With Sts

    USB cable connects to the computer and the other end connects to the USB port on the UPS. Open the Muser5000 software, then touch the “system” button. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 26...
  • Page 28 Shut down the inverter, before using the PC Software to set the output voltage and frequency. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 29: Operation

    ECO mode to increase the efficiency of the power supplied. In ECO mode, the UPS works in Line- KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 30: Startup (On), Shut Down (Off) And Testing Procedures

    LED extinguishes and the inverter LED lights up. The status will be shown on the LCD display. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 31 The rectifier will operate normally after 30 seconds. If the inverter works normally, the system will be KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 32 Wait for about 5 minutes for the internal DC bus and capacitors to completely discharged. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 31...
  • Page 33: Parallel Settings

    3. Open Muser5000 software, click “System”, then select -> “User Set” 4. From “User Set” window click “Set”. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 34 Click “Set” to save the values, as shown below. The UPS will sound a “beep” to indicate that the setting has been correctly saved. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 35: Touch Display And Control Panel - Pages & Settings

    The setting of most parameter cannot be set when the UPS is in inverter mode. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 34...
  • Page 36 Touch the Mains icon to enter the mains data window, touch the Datas icon to jump to the home page. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 37 Touch the Output icon to enter the output data window, touch the arrow icons to view additional data, touch the back icon return to last window. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 38 3.4.3 Touch the Alarm icon to view real-time status of the Current Alarms, Buzzer, History. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 37...
  • Page 39 To turn unmute it and turn it back on, press the green icon and the icon will change to red. Touch the Datas icon jump back to the home page. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 40 Touch the Settings icon to enter settings page, touch on the Datas icon jump to the home page. Touch the Basic Settings icon and enter the user password (default is 111111). KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 41 Touch Language icon to enter setting page, touch the back icon return to last window. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 40...
  • Page 42 Touch Time and Period icon to enter setting page, touch the back icon return to last window. Date has three formats to select from. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 43 Bypass rate tracking rate: Inverter frequency tracking to bypass frequency rate. The value range is 0.5~2 (default is 1). KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 44 Touch on the Datas icon to jump back to the home page. The default password is 191210. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 45 Bypass Rate Tracking Rate: 0.5~2 (default 1). This sets the inverter frequency tracking relative to the bypass frequency rate. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 46 Temp Sensor Select: NTC or RS485 NTC for single and short distances. RS485 for multiple and longer distance. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 47 Output Voltage Level: 110, 115, 120, 127 or 133. Output Inverter Voltage Regulated: -5% ~ 0 ~ +5% (default value 0) step is 0.5%. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 48 Cell Boost Voltage (Equalization Voltage): 2.30–2.40 V/cell (default 2.30 V/cell) Average Charging Duration: 1–999min (default 240 by). This is the boost charge time limit. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 47...
  • Page 49 Battery Abnormal BCB Trip: Enable, Disable (default Disable). Bypass Feedback: Enable, Disable (default Disable). External Maintenance Breaker: Enable, Disable (default Disable). KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 48...
  • Page 50 Touch the Output History (Alarms) icon or Set (Settings) Record Export icon to download data to USB. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 51 Set the Date/Cycle/Day (interval between tests): days/hours/minutes. Set the Check Time (duration of test): 10s, 10min, EOD [End of Discharge], (default 10s). KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 52 Parallel OFF: Inverter OFF for All parallel UPS Parallel ON: Inverter ON for All parallel UPS KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 51...
  • Page 53 Touch Confirm icon to clear faults (Note: not all faults can be cleared using this method, some must be physically be corrected to clear). KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 54 Touch About icon to enter the about page to confirm installed software versions and touch the Datas icon to jump back to the Home page. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 55: Display Messages / Troubleshooting

    Twice per second Fault LED lit Output Short Circuit Once per second Fault LED blinking KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 54...
  • Page 56 Once per 2 seconds FAULT LED blinking ECU Par. cable Once per 2 seconds FAULT LED blinking abnormal KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 55...
  • Page 57 Once per second BYPASS LED blinking Ecu Set Data Err Once per 2 seconds FAULT LED blinking KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 56...
  • Page 58: Optional Cards - Snmp / Relay

    Table: Relay Contacts (communication card) KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 59: Specifications

    Net weight (kg) STANDARDS Safety IEC/EN62040-1, IEC/EN60950-1 IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000- 4-5, IEC61000-4-6, IEC61000-4-8 KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 58...
  • Page 60: Appendix 1 Problems And Solutions

    UPS with AC and set battery set; Power breaker in the rear panel not quantity. Switch ON power breaker. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 59...
  • Page 61: Appendix 2 Usb Communication Port

    USB, RS232 and RS485 interface cannot be used at the same time, only one can be used at any time. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 62: Appendix 3 Rs232 Communication Port

    USB, RS232 and RS485 interface cannot be used at the same time, only one can be used at any time. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...
  • Page 63: Appendix 4 Rs485 Communication Port

    USB, RS232 and RS485 interface cannot be used at the same time, only one can be used at any time. NOTE: RS485 port pin7 is 12Vdc. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only Page 62...
  • Page 64: Ke 4256-Xxxx Keatec T Series 25-100Kva Pf1.0 208Vac With 7.0 Touch Screen Users Guide English

    A remote emergency stop switch can be installed in a remote location and connection through simple wires to the REPO connector. KE 4256-xxxx Keatec T Series 25-100kVA PF1.0 208Vac with 7.0 Touch Screen Users Guide English 20190209 This manual is for qualified personnel only...