Advertisement

UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER
INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION;
(B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL,
DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE
USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER'S RISK; AND
(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO
MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS
CONTAINED WITH THE ENGLISH LANGUAGE.
(D)
INFORMS YOU THE INFORMATION IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE.
(E)
RESERVES ALL RIGHTS.
DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only
DBL MX-U Series UPS
Models 1000U-48, 1500U-48, 2000U-48
Manual

Advertisement

Table of Contents
loading

Summary of Contents for Keatec Energy DBL MX-U Series

  • Page 1 MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE. INFORMS YOU THE INFORMATION IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. RESERVES ALL RIGHTS. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 2: Table Of Contents

    Generator Bypass Operation……………………………………………………..….…..….…..…13 Section 7 Batteries Connections This section left intentionally Blank ...……………………..…….…..…..…..….…....14 This section left intentionally Blank……………………..………………………….………..15 48 VDC Battery Cables …..……..…………………………………..………….……....……16 DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 3 10.1.1 UPS ECO Mode ........................30 10.1.2 UPS Frequency Mode 50Hz....................30 10.1.3 UPS Frequency Mode 60Hz....................30 10.1.4 UPS Output Fine Tuning VAC Values..................30 DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 4 13.1 UPS Power Operational Sequences..................36 Section 14 UPS Problem Solving 14.1 Trouble Shooting………………………………………………………………..……..…37,38,39,40 Section15 Specifications and UPS Data Specifications…………………………………………………………………….……………..41,42 Section Maintenance ……………………………………………….……………………………..52,53,54,55 DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 5: Important Safety Instructions

    60VDC / 40A 33.33A AWG #12 x 2 or AWG #8 DBLMX1000U-48 60VDC / 32A AWG #14 x 2 or AWG #12 DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 6: Characteristics

    The UPS provides numerous configurable output voltages to match a wide range of system voltages. The UPS is designed to comply with various stringent international standards for electromagnetic interference compatibility (EMC) as well as FCC classification. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 7: Standard Features

    • DC battery preconfigured interconnect cable assembly (3) • User Manual (1) • Software disc and USB cable (1 ea) • EPO connector (1) DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 8: Ups Front Panel View

    Section 4 4.1 Front Panel Views DBLMX1000U-48 DBLMX1500U-48 DBLMX2000U-48 DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 9: Control Panel Functions

    Go to next page Go to previous page or change the setting of the UPS. To re-confirm the change of UPS Settings DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 10: Control Panel Symbols And Icons

    UPS Fault or Abnormal Warning UPS Flow Chart 3-Digit Measurement Display Indicates the item to be measured Battery Abnormal Battery Low Testing DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 11: Secondary Timer Display

    2) 3 Button Programming, set, scroll, next. 3) Charge Status LED 4) Timer Function LED 5) Timer, Counter, Hours 6) TempProbe Connector DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 12: Communication Ports

    (highest priority first). This is the layout, located on the right side the LCD control panel. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 13: Ups Systems Block Diagram

    4) A bank of stationary, maintenance-free batteries 5) A DC-to-DC push/pull converter control circuit 6) A static bypass loop 7) Input and output EMI filters DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 14: Operating Modes

    Quick and short successive beeps Confirm RS-232 port receiving two quick and short beeps Service mode okay one quick and short beep DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 15: Bypass Switch

    White: These (1 or 2) are Neutrals for the Utility Input and UPS output, they are always common. Red: This is the UPS Output Line (LOAD). Green: This is the UPS and Bypass Grounding conductor. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 16: Hsu-1500 Operation

    WILL TRANSFER UTILITY POWER DIRECTLY TO THE EQUIPMENT. The Bypass will automatically transfer into a BYPASS position and the RED LED will be ON AC IN Load DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 17: Generator Bypass Hsu Dual

    WHITE: AC OUTPUT NEUTRAL BLACK: AC INPUT BROWN /ORANGE: GENERATOR WHITE: AC INPUT NEUTRAL WHITE: GENERATOR NEUTRAL RED: UPS OUTPUT TO LOAD DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 18: Generator Bypass Operation

    THE FAILSAFE BYPASS WITH GENERATOR WILL ALWAYS SELECT THE LINE (utility) WHEN IT IS PRESENT, THIS IS CALLED (LATCHING TO LINE). THIS FEATURE CANNOT BE CHANGED !!!. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 19: This Section Left Intentionally Blank

    SECTION 7 This Section Intentionally Left Blank DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 20: This Section Left Intentionally Blank

    7.2 This Section Intentionally Left Blank. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 21: Vdc Battery Cables

    7.3 48 VDC Battery Cables 30 cm DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 22 7.4 Battery Configuration (48VDC) *MX-1000U-48/,1500U-48/,2000U-48 Layout View of the 48VDC Battery Harness 48.00 DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 23: This Section Intentionally Left Blank

    7.5 This Section Intentionally Left Blank. 7.6 This Section Intentionally Left Blank. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 24: This Section Intentionally Left Blank

    This Section Intentionally Left Blank. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 25: Battery Temperature Probe

    NOTE: If the probe is not connected, the UPS will continue to charge the batteries, but not optimize the DC voltage for temperature. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 26: Section 8

    1) You will notice Black with a Green (PP-30) connector. 2) One latching end is inserted into the 6-Pole Anderson power connector on the UPS. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 27: Section 9

    Section 9.0, will cover the Start Up of the UPS when all the cables and terminations have been made. For the Timer and Relay Outputs, go to section 12. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 28: Ac Input Voltage

    Before initiating the first backup test, always make sure that the batteries installed are completely charged all of the DC cables and battery cable ends are tight. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 29: Input Frequency

    The UPS parameters can be viewed with the UPS after start up or in a normal operating mode. Use the select down key. The display sequences are as follows. Figure-F (AC input voltage) Figure-G (AC input frequency) Output Voltage DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 30: Ups Output Frequency

    Figure-I (UPS output frequency) Figure-J (UPS loading percentage) Figure-K (UPS output current) Figure-L (Battery String voltage)  9.1.1 Figure-M (UPS inner temperature in C) DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 31: Audible Alarm

    If AC is applied to the UPS at any time during this operation, then the charger will begin charging the batteries. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 32 Proceed and follow the start-up instructions in section (2) If the alarm has not cleared proceed to the Alarm code section on page….. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 33 This the Self-Test function of the UPS, It may be set to off so that the MX-U will perform an Auto test. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 34: Bypass Vac Window

    Figure V2 The UPS is operating in “Eco mode”. This indicates that the UPS is operating in a Economy mode and is operating in an energy saving mode. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 35 50Hz to 60Hz mode. 10.1.4 Figure W (Output Voltage Fine Tune Values)  Output Voltage Adjustment (-3%, -2%, -1%, 0%, +1%, +2%, +3%) DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 36: Changing The Ups Parameters

    After completing the changes, you must scroll to the “End” screen. key to save all of your changes and then press the enter * Press the Enter key to save changes. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 37: Turn Off The Ups In Dc Mode

    2 seconds to change the UPS operation. Once UPS is switched to Normal Mode, the Bypass LED or symbol will be “OFF”. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 38: Timer Programming

    11.3 Display Screens 1 st Line Titles / Status Messages Scr#1 2 nd Line On-battery Timer | Accumulated On-battery Hours | Events Counter DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 39: Key Functions

    After Incr Key, restore previous View After Incr Key, accept new value Next Increment parameter to next value Incr Clear parameter to least value Next+Incr DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 40: Ups Relay Output Card

    When the applied signal has been removed, the UPS must be reset because this is a latched alarm. Meaning that you must disconnect the AC and DC, then reconnect and restart the UPS normally.. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 41 Communication expansion slot: Provides a hot-swappable slot for the optional interface card; provides development and application for diverse needs. Optional interface cards: Includes SNMP card, dry contact card, RS-232 card and USB card. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 42: Trouble Shooting

    Remove all DC and AC Line connections. Connect the Switches to bypass for 1 batteries, perform DC Cold- minute then back to Inverter. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only.
  • Page 43 Line Charger out of order Er13 Battery Low(11.2nV), then batteries. lock the UPS Has there been a long power failure. Add ABM. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 44 Lock the UPS, then show error Bypass Bypass overload Er28 Check for ventilation code & alarm obstructions. Is the UPS clean. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 45 Low Battery automatically. batteries. Has there been a power failure. Line Alarms until Battery Low, then lock the UPS and shows ER13. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 46: Specifications

    >150% Immediately transfer to bypass. Buzzer continuously alarms. Line mode >90% Efficiency Battery mode >86% ECO mode >96% Battery String Qty. DC Connection Anderson 4 p DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 47 UPS shuts down immediately N/C or NC option. Normal Mode :Transfer to Bypass Mode Battery Mode : UPS Over Temperature shuts down immediately DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 48 RS-232, EPO,Relay Contact Board, Timer Relay, Fault Relay, Low Battery Relay Interface Optional SNMP/Ethernet Communications Compatible Microsoft Windows series, Linux, Mac, etc. Platforms cTUVus Safety Standards FCC Part 15 Class A Certifications DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 49: Section 16 Maintenance

    String VDC The batteries must be with 2 x Tenths of a VDC to be considered “optimal “ in a UPS application. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...
  • Page 50 If the batteries have all passed the testing and the batteries are not equal, the batteries should be removed from the string and charged individually. Or a battery ABBM battery balancer should be installed. DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English 20180312 - This manual is for qualified personnel only...