Analyzing Discharge Line Temperature - Manitowoc UDE065A Technician's Handbook

Neo series undercounter ice machines
Table of Contents

Advertisement

ANALYZING DISCHARGE LINE TEMPERATURE

1. Determine the ice machine operating conditions:
Air temperature entering condenser ______
Air temperature around ice machine ______
Water temperature entering sump trough
2. Refer to "Installation/Visual Inspection Checklist" on
page 136 for ice machine being checked.
Use the operating conditions determined in step 1 to find
the published normal discharge temperatures.
Freeze Cycle
Harvest Cycle
3. Perform an actual discharge temperature check.
Beginning of
Cycle
Middle of
Cycle
End of
Cycle
4. Compare the actual discharge temperature (Step 3)
with the published discharge temperature (Step 2).
The discharge temperature is normal when the actual
temperature falls within the published temperature range
for the ice machine's operating conditions. It is normal for
the discharge temperature to be lower at the beginning of
the freeze cycle, then climb through out the freeze cycle.
142
______
______
Freeze Cycle
Temperature
__________
__________
__________
Part Number 000014797 Rev02 05/18
______
Harvest Cycle
Temperature
__________
__________
__________

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents