L300P-450L - Hitachi L300P-110L Instruction Manual

L300p series three phase input 200/400v class
Table of Contents

Advertisement

6.1Standard specification list
L300P
Inverter Model
110LF
Enclosure
(Note 1)
Max. Applicadie Motor 4P
11
(kW) (Note 2)
200V
15.2
Rated input
Alternating
voltage(kVA)
240V
18.2
Rated input alternating
Three-phase 200-240V (±10%) 50Hz/60Hz
voltage
Rated output voltage
Three-phase 200-240V (This corresponds to receiving voltage.)
(Note 3)
Rated output current (A)
44
Control system
Sine-wave modulation PWM system.
Output frequency range
0.1-400Hz
(Note 4)
Frequency accuracy
Digital command ±0.01% for Max. frequency, analog frequency ±0.2%(25±10ºC)
Frequency resolving
Digital setting: 0.01Hz, analog setting:Max. frequency /4000
power
Voltage/frequency
V/f option variable, V/f control, (constant torque, reduced torque)
characteristic
Overload current rate
120% for 60 seconds, 150% for 0.5second
Acceleration/
0.01-3,600seconds (straight or S-Curve on acceleration, deceleration is optional setting individually), 2
deceleration time
Regenerative
Control
BRD circuit built-in
(short duration)
(Discharge resis-tance is required.)
(Note 5)
On starting and decelerating by stop command, inverter operates under operation setting frequency. Or inverter operates with external input
DC Braking
(Breaking power, time, frequency can be set.)
Setting by
Operator
Setting with potentiometer on the digital operator (Built-in as standard) (Analog setting)
Volume
Freq-
External
DC 0 to 10V, -10 to +10V (input impedance 10k ohm), 4 to 20mA (input impedance 100 ohm)
uency
Signal
External
Setting with RS485 communication
port
Run/Stop (forward changes with code)
Operator
External
Run/
Forward Run/Stop (1a connect), reverse command is impossible on assigning of terminal (selection of 1a, 1b is possible), input of 3 wires is possible.
signal
Stop
External
Setting with RS485.
port
Use by selecting terminals from;
Reverse command (RV), multi-speed1-4 (CF1-CF4), jogging (JG), external dc braking (DB), 2
Intelligent input
USP function (USP), commercial change (CS),software lock (SFT), analog input voltage / current / select (AT), reset inverter (RS), 3 wire run (STA),3 wire keep (STP),
terminal
3 wire direction selection (F/R), PID selection valid/invalid (PID), PID integrating reset (PIDC), remote control,up function (UP), remote control down function (DWN),
remote control data clear (UDC), multi-speed bit 1-7(SF1-SF7),overload ristriction change (OLR), no assign (NO)
Thermistor input
1 terminal
terminal
Intelligent output
2 relay outputs (1a contact), relay(1c contact), output relay selection as follows;
terminal
(selection from during running, on arrival with constant speed, over setting frequency, PID over-deviation)
Intelligent monitor
Analog voltage output, analog current output, pulse line output
output terminal
Display monitor
Output frequency, output current, frequency conversion value, trip history, input output terminal state, input electric power, output voltage.
V/f free setting (5 points), Upper / lower frequency limitter, Frequency jump, Curve adjustable speed, Manual torque boost level / Braking point,Analog meter adjustment,
Other function
Starting frequency, Carrier frequency adjustment, Electronic thermal free setting, External start/end (frequency/rate),Analog input selection, Trip retry, Reduced voltage start,
Overload restriction
Carrier frequency
0.5-12 kHz
range
Over-current, over-voltage, under-voltage, electronic thermal level, abnormal trouble, ground fault current on starting, instantaneous stop, USP error, open-phase error, control resistor
Protection function
overload, CT error, external trip, communication error
Frequency
temperature
/Preservation
-10 to 40ºC (Note 10) / -20 to 65ºC / 20 to 90% RH (installed with no dew condensation)
temperature
(Note 6) /humidty
Vibration (Note 7)
Using place
Under 1,000m above sea level, indoors (installed away from corrosive gasses, dust)(Note 8)
Paint color
Blue (D.I.C14 version No.436)
Operator with copy function, cable for operator, braking resistor, regenerative control unit, alternating reactor, D.C. reactor, EMC Mains filter, higher harmonic
Options
control unit, LCR filter, applied control installation
Remote operator
OPE-SR, cable for remote operation ICS-1(1m), ICS3(3m) (Note 9)
Schematic mass (kg)
5
(Note 1) Protective system bases on JME1030.
(Note 2) Applicable motor indicates HITACHI three-phase motor. When you use other motor, set so that the motor current doesn't exceed the rated current of the inverter.
(Note 3) Output voltage will reduce when the power voltage is reduced. (Except when AVR function is selected.)
(Note 4) When you operate motor over 50/60Hz, inquire about the allowable max.revolution time of motor etc. from motor manufacturer.
(Note 5) Braking resistance isn't installed in the inverter. When the inverter requires a high regenerative torque, use optional braking resistance and regenerative braking unit.
(Note 6) Protective temperature is temperature during transportation.
(Note 7) This bases on the test methods of JIS C0911(1984).
(Note 8) When the inverter is used in a place with dust, we recommend the optional varnish coating specification. Before it is required.
(Note 9) When you use cable for remote operation, please remove connector. Please refer to 1.3 Appearance.
(Note 10) When using at 50ºC of ambient air temperature, the rated output current will be reduced. (P.4-18)
(Note) Insulation distance is based on UL, CE standard.
L300P
L300P
150LF
185LF
15
18.5
20.0
25.2
24.1
30.3
58
73
2
keys
1
2
5.9m
/ S (0.6G), 10-55Hz
5
12
200V class
L300P
L300P
L300P
220LF
300LF
370LF
IP20(NEMA1)
22
30
37
29.4
39.1
48.4
35.3
46.9
58.1
85
113
140
nd
adjustable setting is possible.
Regenerative unit is required.
nd
nd
control (SET),2
acceleration (2CH), free-run stop (FRS), external trip (EXT),
Gray(MUNSELL 8.5YR6.2/0.2)
12
12
6-1
Chapter 6 Specification
L300P
L300P
450LF
550LF
45
55
58.5
72.7
70.2
87.2
169
210
2
2.94m
/ S (0.3G), 10-55Hz
20
30
30
L300P
750LF
75
93.5
112.2
270
50