Voltage indicator

Advertisement

VI13700g voltage ind instruct rev5:instruct.qxd
Never apply more than the rated voltage (600V max) between the probe tips.
Try to use the unit with the retractable shrouds extended to minimise the risk of flashover.
When using the probe ensure your fingers are behind the finger guard.
Do not operate the tester around explosive gas, vapour or dust.
NEVER TOUCH THE EXPOSED METAL PROBE TIPS.
SPECIFICATION
Voltage Range: 50 to 600V AC RMS
75 to 600V DC
Frequency Range: 0Hz to 400Hz & DC
Power Consumption: approx. 4W at 600V
Temperature Range: -10°C to 40°C at max. 60% RH
Fuse Rating: 0.5A fast (600V)
Overvoltage Category: 600V Cat. 3
Pollution Degree: 2
Neon Strike Voltage Tolerance: -30% to +5%
+
~
MAINTENANCE
Cleaning
The unit may be cleaned using a soft dry cloth. Do not use moisture, abrasives, solvents, or
detergents, which can be conductive.
Repair & Service
There are no user serviceable parts in this unit other than fuses. Return to Martindale Electric if faulty.
Before returned, please check the unit, fuses, leads and poor connections
Storage Conditions
The instrument should be kept in warm dry conditions away from direct sources of heat or sunlight.
Metrohm House, Penfold Trading Estate, Imperial Way, Watford WD24 4YY, UK
E-mail: sales@martindale-electric.co.uk
Registered in England No. 3387451. Document Rev 5 LITVI
approx. 0.4W at 230V
+
~
VOLTAGE
RANGE
50
75
100
Trusted by Professionals
Martindale Electric Company Limited
Tel: +44(0)1923 441717 Fax: +44 (0)1923 446900
© Martindale Electric Company Ltd. 2009
10/03/2009
11:56
OPERATION
1. Observe all safety recommendations
before use.
2. Apply the flying probe to the earth or lower
voltage terminal (if known) with one hand
ensuring fingers are behind the guard.
DO NOT TOUCH METAL TIPS.
3. Touch the fixed probe to the suspected live
terminal. Neons will strike progressively
to indicate the presence of AC or DC voltage.
150
200
240
400
560
Website: www.martindale-electric.co.uk
Page 2
Light On
Light Off

Advertisement