en | Installing
4

Installing

4.1

Installation Precautions

To avoid incorrect installation and operation, strictly observe the following precautions:
Caution!
Incorrect system operation
Follow all instructions in this manual. Do not deviate.
!
Comply with all codes and standards set forth by the Authority Having Jurisdiction (AHJ).
Do not assume any installation details not shown in this manual.
Do not alter any mechanical or electrical features of the equipment supplied.
Notice!
Within this document, FPA-1000 refers to both the FPA-1000-UL and FPA-1000-V2. Reference
to a complete identifier (FPA-100-UL or FPA-1000-V2) indicates the text applies to only that
product/system.
Extent/limitations of synchronization
There are two mainboard NACs on each panel that are synchronized with one another.
Separate panels are not synchronized with each other.
You can add up to four addressable FPP-RNAC-8A-4C NAC power supplies. These remote
power supplies provide Aux power and up to 16 synchronized remote NAC circuits. They are
not synchronized with the mainboard NACs, but they are synchronized with each other.
Some signaling line devices function as NACs (for example, sounder bases or strobes). The
SLC devices that are on the same SLC are synchronized with each other, but they are not
synchronized devices on the other SLC nor with the mainboard or RNAC NACs.
4.2

Installation Considerations for UL Listed Systems

Install the control panel according to NFPA 72 for Commercial Fire installations.
Failure to install and program this equipment according to the following requirements voids
the listing mark of Underwriters Laboratories, Inc. (UL).
When used in UL Listed installations, the control panel must conform to certain programming
requirements. Refer to UL 864 Standard-specific Requirements, page 43.
2017.11 | 2.0 | F.01U.173.607
The standby battery capacity is:
Up to 18 Ah at 24 VDC with batteries within enclosure
Up to 40 Ah at 24 VDC with batteries in separate battery box
Above 40 Ah at 24 VDC with UL Listed external power supply
The total nominal system current must not exceed:
1.25 A in standby
or 4.0 A shared between NAC, Option Bus and AUX power when in alarm
or 5.0 A shared between NAC, Option Bus, AUX power, SLC and panel when in alarm
The control panel must be mounted dry indoors and within a protected area.
Grounding must be according to Article 250 of the National Electrical Code (NEC)
(NFPA 70).
Points must be connected to UL Listed, compatible devices.
The ground wire provided with the enclosure must be connected between the door and
the enclosure, using the supplied nuts.
Installation and Operation Guide
Analog fire panels
Bosch Security Systems, Inc.