Advanced Point Features And Processing - Bosch FPA-1000-UL Installation And Operation Manual

Analog fire panels, fpa-1000 family
Hide thumbs Also See for FPA-1000-UL:
Table of Contents

Advertisement

26
en | Planning Information
3.3.2

Advanced Point Features and Processing

The panel provides flexible handling on a point so that more optional features are
accomplished. These features are applicable to specific types. The control panel lists only
possible point features for that point type when programming on menu and Web pages.
For mapping of point type to available point features, see the following table.
Point type
Fire
Automatic
Fire Alarm
Manual
Waterflow
Waterflow
delay
Gas Alarm
Supervisory
Generic
AC Failure
General
Fire Alarm
AV = Alarm Verification
PAS = Positive Alarm Sequence
D = Day, N = Night
1)
Tab. 3.14: Mapping point types to point features
The following principles apply:
Delay options can be selected individually for each SLC Fire Automatic input.
To program an SLC device:
The following table shows the prioritization of both delay settings:
Fire Automatic Input
No delay
2017.11 | 2.0 | F.01U.173.607
Latching
X
X
X
X
X
G
X
Not for FAH-325
For Supervisory point type, programming of latching or non-latching is panel-wide.
The point types Generic, Trouble, AC failure, Battery Failure, Reset, Silence, Drill, and
Acknowledge are non-latching (see Points, page 24).
For the Fire Automatic point type, only one of three programmable features can be
selected - AV, or PAS/Pre-signal or PAS (Day)/AV (Night). AV and PAS (Day)/AV (Night) do
not apply for the FAH‑325 Analog Heat Detector.
By keypad, use shortcut 6-1 for PROGRAMMING-SLC DEVICES (see Shortcuts, page 91
and/or Menu Structure, page 92)
By browser, program SLCs on the SLC 1 and/or SLC 2 screens
Programming SLC
Installation and Operation Guide
Point feature
AV
PAS/
Pre‑signal
1)
P
P
X = Fixed point feature
P = Programmable point feature
G = Dependent on global setting
Blank = not available
Day Mode (Site Data)
No delay
No delay
PAS (D)/
Waterflow
AV (N)
delay
1)
P
X
PAS
Pre-signal
No delay
Bosch Security Systems, Inc.
Analog fire panels
AC fail
delay
X
No delay

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fpa-1000-v2

Table of Contents