Vertical Outlet For Pitched Or Flat Roofs - Viessmann Vitocaldens 222-F Installation Instructions Manual

Flue system for condensing boilers
Table of Contents

Advertisement

Installation in a disused chimney
07. Pull balanced flue pipe D down-
wards and push it into the boiler
flue connection as far as it will go.
Ensure that the gasket is seated
correctly in chimney connection
plate C.
08. Tighten the fixing screws of chim-
ney connection plate C.

Vertical outlet for pitched or flat roofs

If the balanced flue system is routed
through roof spaces that are not used
as accommodation, run the flue through
an additional metal pipe as protection
against mechanical damage
(TRGI 2008).
(cont.)
09. Secure balanced flue pipe D to
chimney connection plate C with
the self-tapping screw supplied.
10. Fit the shaft cover. See page 33.
When several roof outlets are installed
side by side: Observe a minimum clear-
ance of 1.5 m between outlets and to
other building structures (e.g. skylights)
in accordance with TRGI 2008.
Observe the clearance of the flue outlet
above the roof (see diagram). If the
rated heating output is ≥ 50 kW, an
above-roof extension is required (see
page 46).
41