Connections on the heating water side
Danger
There is a risk of injury when working on pres-
surised components.
Only open the connections on the heating water
side after the boiler has been depressurised.
Note
■
The boiler is only suitable for fully pumped hot water
heating systems.
Install all pipe connections free of load and torque
■
stress.
1. Thoroughly flush the heating system.
Connections on the flue gas side
Flue outlet and siphon
1.
Fig. 10
1. Insert the boiler flue connection (Vitoset accesso-
ries) into the flue outlet as far as it will go.
Note
Connect the flue outlet to the flue pipe via the
shortest possible run, with a slight incline (min. 3
Avoid sharp bends.
(cont.)
2. Note
Never connect heat consumers to the safety con-
nector.
Make all necessary connections. Connecting a sin-
gle heating circuit: Connect the heating return to
boiler return 1.
Connecting two heating circuits: Connect the heat-
ing circuit with the higher temperature level to
boiler return 2.
Connect at least 15 % of the boiler heating output
to boiler return 1.
Close test ports that are not used for the installa-
tion of a measuring probe or sensor.
3.
2. Connect the flue system.
Internal
187 to 314 kW: 201 mm
408 to 635 kW: 251 mm
).
º
Flue system installation instructions
Note
Make all connections free of load and torque
stress.
We recommend providing separate support for the
flue system.
3. Fill the siphon with water and fit it to the boiler.
of the flue outlet for: