Viessmann Vitocaldens 222-F Installation Instructions Manual page 29

Flue system for condensing boilers
Table of Contents

Advertisement

Routing through a shaft
Maximum flue length
Vitodens 100-W, type B1HA and B1KA, Vitodens 111-W
Rated heating output
System size 80
Note
For system size 80, an adaptor is
required.
Vitodens 200-W, 222-F and 242-F
Rated heating
output
System size 60
System size 80
System size 100
The following components are taken
into consideration for the maximum flue
lengths:
■ Connection pipe 0.5 m long
■ 1 flue bend 87° and 1 support bend
87°
or
■ 2 flue bends 45° and 1 support bend
87°
Installation
Danger
To ensure correct function, route
the flexible flue at a maximum
angle of 45° from the vertical.
Never pull the flexible flue pipe
over sharp edges during instal-
lation.
Note:
■ Always draw the flue pipe in from the
top downwards.
■ Observe flow direction (arrow on
components).
(cont.)
kW
m
kW
13
m
18
m
25
m
19
20
19
26
35
18
25
25
25
Subtract other bends, tees and straight
lengths from the maximum length using
the following values:
■ Connection pipe 0.5 m long: 0.5 m
■ Connection pipe 1 m long: 1 m
■ Flue bend 45°: 0.3 m
■ Flue bend 87°: 0.5 m
■ Inspection tee: 0.3 m
■ Subject to shaft size, install spacers
at intervals of max. 2 m.
■ Insert a spacer before and after any
change in direction and any inspec-
tion piece.
■ The flue must not come into contact
with the shaft wall.
26.0
30.0
20
25
45
60
80
20
15
22
17
20
35.0
25
100
20
29