• Each side of the unit must be located at least 300mm from walls, pipes, or other obstructions
for unrestricted air intake and service access.
Do not install the unit within 1m of fossil fuel burning heaters. Air intake
along the sides of this heat pump could disturb the combustion process
of the unit, and could cause damage or personal injury.
• Mount the unit on a level, sturdy base, preferably a concrete slab or blocks. The size of the
base should be not less than 1m by 1m.
• Completely isolate the base from the building foundation or wall to prevent sound or
vibration transmission into the building. For this purpose, 4 black rubber sound isolation
pads are included with the unit. These pads must be installed under the corners of the
unit to reduce vibration and sound transmission to the base.
• If the unit is installed in an area known for water accumulation during periods of heavy
rainfall, its supporting base must be high enough to keep it completely free of standing water
at all times.
II. Electrical Connections
The table below lists the typical electrical power requirements for your heat pump.
Table 1: Typical System Electrical Power Requirements
Model
RHP 33
Refer to the unit rating plate below the control panel for precise power requirement for each unit,
and for ampacity and over-current protection requirements. All wiring must be in accordance with
the AS3000 Wiring Rules Section 7.2 Swimming Pools, latest edition, and all applicable state
and local codes.
The power supply connections to the unit are located behind the control panel. Remove the
control panel to expose the electrical controls. Line voltage connections are made at the line
voltage terminals of the compressor contactor. Refer to the Heat Pump Schematic (page 11) and
the Control Panel Assembly Replacement Parts List (page 12).
Conduit entrance to the unit is through a hole below the control panel.
NOTE: Make certain all electrical connections to unit terminals are secure.
WARNING
V
- Phase - Hz
IN
240 - 1 - 50
Min. circuit Ampacity (A)
42.2
2
Max. breaker size (A)
60