Optional Features - Honeywell OmniClass OM15 Installation Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
1
Mounting
Junction box not
included
Gasket optional
2
Wiring
18 in
(0.46 m)
PIGTAIL***
TERMINAL
Yellow
P1-1
Orange
P1-2
Black
P1-3
Red
P1-4
Drain
P1-5
Brown
P1-6
Blue
P1-7
Red/Green
P2-7
Tan
P2-6
Violet
P2-5
White
P2-4
Green
P2-3
Pink
P2-2
Gray
P2-1
* Tamper Output. When activated, output syncs to ground (default).
** Dependent upon reader configuration. See HTOG Wiegand and Clock-and-Data configurations for more
information.
*** For 5 meter pigtail readers, PN: 9xxxxxLEKxxxxx follow the wiring diagram on the reader.

Optional Features

Open Collector Output - Controls an external device (5 VDC) operating in Host Mode only. Sink – 40mA / Source – 1mA.
Configuration Cards – With the use of configuration cards, the reader can be modified to meet the specific requirements of an installation. Configuration options include; audio
visual, CSN outputs and keypad outputs (keypad models only). Contact HID Technical Support for all reader configuration options.
Hold Input – when asserted, this line either buffers a card or disables a card read until released, as configured.
INSTALLATION GUIDE
R10E/RP10E/R10MA/RP10MA, R15E/RP15E/R15MA/RP15MA, R40E/RP40E/R40MA/RP40MA, RK40E/RPK40E/RK40MA/RPK40MA
ATTENTION
Observe precautions for handling
ELECTROSTATIC SENSITIVE DEVICES
BEEP
GPI01
P1
GRN
GPI02
GND
OC/TMPR
+VDC
DATA1/CLK
DRAIN
DATA0/DATA
P2
RED
GPI03
HOLD
GPI04
DESCRIPTION
Beeper Input
LED Input (GRN)
Ground (RTN)
+VDC
Unused
LED Input (RED)
Hold Input
GPI01/OSDP (RS485-FDX/HDX-A)
GPI02/OSDP (RS485-FDX-HDX-B)
*Open Collector Output/Tamper
**Wiegand Data 1 / Clock
**Wiegand Data 0 / Data
GPI03 (RS485-FDX-Z)
GPI04 (RS485-FDX-Y)
3
Install Reader to Backplate
4
Power & Testing
Turn on power
Note: Previous OmniClass readers had reversed RS-485 wiring (P2-7 & P2-6 - A
& B). When upgrading to an OmniClass SE reader, ensure proper connections as
defined below.
Note: It's possible to reuse existing Wiegand wiring for OSDP, however, using simple
stranded cable typical of Wiegand access control readers is usually not meeting the
RS485 twisted pair recommendations.
Note: For OSDP cable lengths greater than 200ft. (61M) or EMF interference, install
120Ω +/- 2Ω resistor across RS-485 termination ends.
Note: Wiring the reader incorrectly may permanently damage the reader.
Note: With a keypad reader, operating as 26 bit emulation; upon power up you have
5 seconds to enter the facility code followed by #. If unsuccessful, the reader LED
displays solid Red. Power-cycle the reader and retry entering the facility code.
The facility code needs to be manually entered as 3 digits (i.e. if facility code is 10
enter 0-1-0-#). Note: OmniClass 2.0 readers only use facility codes between 1-255,
and there is no default facility code. Once the facility code has been entered, the LED
will display Violet and then to a final Red. Then power-cycle the reader. Note: When
using a keypad, if there are 2 short beeps after entering your PIN, the reader does
not have a facility code configured yet. In this event, an Admin will need to be power-
cycle the reader and enter the facility code before the reader will accept your PIN.
Page 2
OmniClass 2.0
OM15/16/17/18, OM30/31/32/33, OM40/41/42/43, OM55/56/57/58
Test card
PLT-01558, Rev A.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents