Siemens 3AK Operating Instructions Manual page 15

Vacuum circuit-breaker module
Table of Contents

Advertisement

Mechanism box
Functions
Indicators
9229 9923 176 0B
2013-09-09
The mechanism box (60.) contains all the electrical and mechanical components
required to switch the vacuum circuit-breaker module on or off. Insulating operating
rods (48.) transfer the switching movement to the pole assemblies.
The mechanism box is closed with a removable cover (60.1).
Fig. 9
Operating and indicator elements
50.1
Opening for hand crank
51.
Rating plate
53.
CLOSE pushbutton
54.
OPEN pushbutton
55.
Spring state indicator
There are openings in the cover (60.1) for the operating and indicator elements.
The CLOSE pushbutton (53.) is used to close the vacuum circuit-breaker module.
The motor (50.4) immediately charges the closing spring (62.). If the supply voltage
for the motor fails, the closing spring can be charged with a hand crank (50.). There
is an opening (50.1) for this in the cover, behind which you will find the hand crank
coupling (50.5) of the gear unit (50.2).
The charged state of the springs is indicated via the spring state indicator (55.). The
position indicator (59.) shows the CLOSED or OPEN state. The operating cycle
counter (58.) indicates the number of operating cycles. An operating cycle consists
of one closing and one opening. The rating plate (51.) is attached to the pole plate
(15.).
58.
Operating cycle counter
59.
Position indicator CLOSED-OPEN
60.1
Cover
a)
Tightening torque Md = 10 Nm
Description
15