FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES

Function
NO
1
Indoor fan
Stops operation if no revolution pulse
lock
signal is input from the indoor fan motor for
one minute.
Indoor fan
Stops operation if the revolution pulse
rpm error
signal from the indoor fan indicates low
rpm (approximately 300 rpm or less).
2
Indoor
Lowers the operating frequency if the
freezing
temperature of the indoor heat exchanger
guard
goes below 5°C during cooling. Stops the
compressor if the temperature stays below
0°C for 4 minutes.
3
DC
Stops the compressor if a current of
overcurrent
approximately 30A or more flows in the
power transistor module. Also stops the
compressor if the temperature of the
power transistor module is exceeds 105°C.
4
AC
Lowers the operating frequency if the
overcurrent
compressor AC current exceeds
set valve( ).
Stops the compressor if the current
exceeds at 40Hz or less set valve( ).
5
Compressor
Stops the compressor if the compressor
lock
AC current exceeds 3A immediately after
activating the compressor (at 10 to 30Hz).
6
Compressor
Lowers the operating frequency if the
overheating
temperature of the compressor chamber
control
thermistor (TH1) rises above 105°C.
Stops the compressor if the thermistor
stays above 105°C for 1 minutes at 35Hz
or less.
7
Compressor
Stops the compressor if the compressor
high
chamber thermistor is above 114°C.
temperature
(Or when TH1 shorts)
error
( )
Model
Set value (Normal)
AU-S22AW2
AU-S25AW2
Operation
Description
6.2A
6.5A
Detection
Restart
time
condition
When indoor
Operation OFF
fan is revolving
During cooling
Automatically
and dry of full
restarts when the
power
exchange
operation.
temperature rises
above the freezing
prevention
temperature (above
2°C)
Automatically
restarts after safety
During
time (170 seconds)
compressor
operation
Automatically
restarts after safety
During
time (170 seconds)
compressor
operation
Automatically
restarts after safety
Immediately
time (170 seconds
after
compressor
activation.
Automatically
restarts after safety
During
time (170 seconds)
compressor
operation
Automatically
restarts when
During
thermistor (TH1)
operation
temperature falls
below 100°C
(approximately 30
minutes)
19
AH-S22AW2
AH-S25AW2
Self diagnostic
display
Restart
Indoor Outdoor
times
No limit
Yes
No
No limit
No
No
4 times
Yes
Yes
4 times
Yes
Yes
4 times
Yes
Yes
No limit
No
No
4 times
Yes
Yes