Function And Operation Of Protective Procedures - Sharp AH-X079E Service Manual

Table of Contents

Advertisement

FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES

Function
NO
1
Indoor fan
Stops operation if no revolution pulse
lock
signal is input from the indoor fan motor for
one minute.
Indoor fan
Stops operation if the revolution pulse
rpm error
signal from the indoor fan indicates low
rpm (approximately 300 rpm or less).
2
Indoor
Lowers the operating frequency if the
freezing
temperature of the indoor heat exchanger
guard
goes below 5°C during cooling. Stops the
compressor if the temperature stays below
0°C for 4 minutes.
3
Indoor
Lowers the operating frequency if the
overheating
temperature of the indoor heat exchanger
control
rises above the overheating temperature
during heating. Stops the compressor if the
temperature stays above the overheating
temperature for 1 minute at 35Hz or less.
Set values for overheating temperature
During normal operation: 46°C to 54°C
During full power operation: 49°C to
58°C
4
DC
Stops the compressor if a current of
overcurrent
approximately 30A or more flows in the
power transistor module. Also stops the
compressor if the temperature of the
power transistor module is exceeds 105°C.
5
AC
Lowers the operating frequency if the
overcurrent
compressor AC current exceeds
set valve( ).
Stops the compressor if the current
exceeds at 40Hz or less set valve( ).
6
Compressor
Stops the compressor if the compressor
lock
AC current exceeds 3A immediately after
activating the compressor (at 10 to 30Hz).
( )
Model
During cooling
AU-X079E
AU-X099E
AE-X079E
AE-X099E
Description
Set value (Normal)
During heating
5.8A
6.0A
6.3A
5.8A
6.0A
6.5A
Operation
Detection
Restart
time
condition
When indoor
Operation OFF
fan is revolving
During cooling
Automatically
and dry
restarts when the
exchange
temperature rises
above the freezing
prevention
temperature (above
2°C)
During heating
Automatically
restarts when the
exchange
temperature goes
below the
overheating
temperature.
During
Automatically
compressor
restarts after safety
operation
time (170 seconds)
During
Automatically
compressor
restarts after safety
operation
time (170 seconds)
Immediately
Automatically
after
restarts after safety
compressor
time (170 seconds)
activation.
21
AH-X079E/X099E
AY-X079E/X099E
Self diagnostic
display
Restart
Indoor Outdoor
times
No limit
Yes
No
No limit
No
No
No limit
No
No
4 times
Yes
Yes
4 times
Yes
Yes
4 times
Yes
Yes

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents