FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES

Function
NO
1
Indoor fan
Stops operation if no revolution pulse
lock
signal is input from the indoor fan motor for
one minute.
Indoor fan
Stops operation if the revolution pulse
rpm error
signal from the indoor fan indicates low
rpm (approximately 300 rpm or less).
2
Indoor
Lowers the operating frequency if the
freezing
temperature of the indoor heat exchanger
guard
goes below 5°C during cooling. Stops the
compressor if the temperature stays below
0°C for 4 minutes.
3
Indoor
Lowers the operating frequency if the
overheating
temperature of the indoor heat exchanger
control
rises above the overheating temperature
during heating. Stops the compressor if the
temperature stays above the overheating
temperature for 1 minute at minimum
frequency.
Set values for overheating temperature
During normal operation: 51°C to 54°C
During full power operation: 54°C to
58°C
4
DC
Stops the compressor if a current of
overcurrent
approximately 30 A or more flows in the
or overheat of
power transistor module. Also stops the
the IPM
compressor if the temperature of the
power transistor module is exceeds 105°C.
5
Lowers the operating frequency if the
compressor AC current exceeds
AC
Peak control level
overcurrent
[11.3A(heating), 10.4A(cooling)]
Stops the compressor if the current
exceeds peak control level at 40 Hz or less.
Stops the compressor if the compressor
AC current exceeds 15 A.
6
Stops the compressor if the compressor
AC current exceeds 4.25 A immediately
Compressor
after activating the compressor (at 17 to 30
lock
Hz).
Operation
Description
When indoor
fan is revolving
During cooling
and dry
During heating
During
compressor
operation
During
compressor
operation
Immediately
after
compressor
activation.
26
Detection
Restart
time
condition
Operation OFF
Automatically
restarts when the
exchange
temperature rises
above the freezing
prevention
temperature (above
2°C)
Automatically
restarts when the
exchange
temperature goes
below the
overheating
temperature.
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Self diagnostic
display
Restart
Indoor Outdoor
times
No limit
Yes
No
No limit
No
No
No limit
No
No
4 times
Yes
Yes
4 times
Yes
Yes
4 times
Yes
Yes