With pump heating circuits, the amount of heat supplied is controlled by switching
the pumps on and off. This is accomplished with 2-position control by means of the
room temperature's switching differential.
°C
TRx
ON
P
OFF
Pump ON
TRx = TRw
Pump OFF
TRx = TRw + SDR
ON
The heating circuit pumps are controlled not directly by the QAA73.110, but by
boiler control. For this reason, this functionality is not ensured by the room unit
alone.
Room temperature setpoint for heating circuit 2. Active only if supported by BMU.
Flow temperature setpoint for heating circuit 2. Active only if supported by BMU.
Room Unit for Boiler Control
Description of room unit settings
Legend
TRx
Actual value of the room
TRw+SDR
temperature
TRw
TRw
Room temperature setpoint
SDR
Switching differential of room
t
temperature
ON
Switch-on point
OFF
Switch-off point
t
Time
P
Pump
Legend
TRx
Actual value of the room
temperature
TRw
Room temperature setpoint
SDR
Switching differential of room
temperature
P
Pump (ON / OFF)
w
Setpoint
°C
Switch-on point
Switch-off point
CE1U2283en
2015-09-16