Check code
HIC pipe temperature thermistor (TH2) open/short
5109
(U4)
Abnormal points and detection methods
Abnormal if TH2 detects to be open/short.
Open: −40 [−40°F] or less
Short: 90 [162°F] or more TH2: Thermistor <HIC pipe>
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting
any connectors, or replacing boards.
Check the wiring and connector connection of TH2.
Is there any abnormality such
as a disconnection, looseness or
breakage?
Disconnect the connector to check the
resistance of TH2 using a tester.
Is the detected resistance normal?
Check a temperature of TH2.
Is the detected temperature normal?
OCH668B
Diagnosis
No
Yes
Yes
Causes and checkpoints
Disconnection or contact failure of connectors
Characteristic defect of thermistor
Defective outdoor multi controller circuit board
The black square (■) indicates a switch position.
Connect the wiring/connector properly.
Yes
Replace it in case of a breakage.
No
The detected temperature of TH2 can be displayed by an
operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2
ON
−99.9–999.9
OFF
1 2 3 4 5 6 7 8
Replace the outdoor multi controller circuit
board
No
(Malfunction of thermistor circuit).
No abnormality
(A connector contact failure is suspected.)
77
Remedy
Replace the thermistor.