DLM PRO Combined DMM, Loop and Socket Tester Instruction Manual & Specification Issue1 09/16 SnS037v1...
Page 2
The DLM PRO is designed to be used by skilled persons in accordance with safe methods of work. If the DLM PRO is used in a manner not specified by Socket & See, the protection provided by it may be impaired.
Page 3
Do not operate the DLM PRO with the battery cover off as this will compromise the insulated safety barrier. To maintain safety, check the tester on a known source or a proving unit such as the Socket & See SP400 before and after use. To ensure serviceability and to monitor accuracy of the DLM PRO, a checkbox such as the Socket &...
Page 4
Loop Impedance Auto Null. Functions test selection. operate from the Functions operate front two 4mm from the top three sockets. 4mm sockets 4mm sockets for VAC, VDC, Continuity, Auto Null functions. The DLM PRO is shown in the loop test function...
Page 5
Continuity checks must be conducted on dead circuits. If a voltage is detected on the terminals while switched to continuity an audible warning will be given and the LCD backscreen will illuminate RED. The DLM PRO is fully protected against accidental mains connection.
Page 6
The tester will not allow a loop test to be carried out if the socket test function detects a fault or if the incoming voltage is not between 195V and 253V AC. Once the Earth Loop Impedance has been measured the DLM PRO backscreen will illuminate and clear written indication of GOOD, CHECK or FAIL will accompany the numerical value displayed.
Page 7
4. Maintenance and Service If required, clean with a damp cloth and mild detergent. Do not use abrasives or solvents. With the exception of the batteries there are no user serviceable parts. Contact Socket and See for parts and technical assistance. Socket &...
Specification Wiring Test Detects missing E or N (>15kΩ) Detects L-E or L-N swap Phase - Neutral voltage measurement accurate to +1% Loop Test (No trip mode, 3 wire testing, Phase - Neutral - Earth all connected) Test current <15mA at 253V AC Auto Range Accuracy 0.00 to 9.99 Ω...
Page 9
Specification Continued Power Supply 4 x AA LR6 Batteries 50 Hours Battery Life CAT III 300V Overvoltage category 0 - 40ºC Operating Temperature -20 to 65ºC Storage Temperature Operating Humidity 0 - 95% @ RH non-condensing Safety Compliance BSEN 61010-2-030:2010 EMC Compliance BSEN 61326-2-2:2013 Probes...
Ordering Information Item Supplier Code Socket and See DLM PRO. Combined DMM, Loop and Socket SOC/DLMPRO Tester Socket and See PDL234Plus. SOC/PDL234Plus Part P Loop testing kit Socket and See SS130. SOC/SS130 Socket Adaptor Socket and See SP400. Proving Unit with Non-Contact SOC/SP400 Voltage Check.