Service & Maintenance manual
Salwico CS4000
136
FEEDBACK FAULT
137
POSITION FAULT
138
LOOP CABLE SHORT
139
LOOP CABLE A SHORT
140
LOOP CABLE B SHORT
CABLE BREAK
141
POSITIVE
CABLE BREAK
142
NEGATIVE
COMMUNICATION
ERROR
143
The communication with
a unit is deficient.
WRONG TYPE OF
144
UNIT
UNKNOWN TYPE OF
UNIT
145
The type of unit specified
is unknown to the system.
146
TIMER STUCK
148
DOUBLE ADDRESS
149
CABLE SHORT
VALVE CLOSED
150
CONFIGURED NOT
151
PRESENT
PRESENT NOT
152
CONFIGURED
HIGH CURRENT ON
153
LOOP
Appendix A: Fault codes & Fuses
External load is
missing.
A supervised unit (for
example a door or
damper) is in the wrong
position.
A short circuit in the
detector loop cable.
Short circuit on the A-
side of a detector loop.
Short circuit on the B-
side of a detector loop
A cable break on the
positive conductor has
been detected.
A cable break on the
negative conductor has
been detected.
Two units have the
same address.
Loop unit faulty.
Interference
The type of unit
specified is different
from the type found or
configured.
Unit faulty
Wrong type of detector
has been installed
The timer has been
activated too long.
Two units sharing the
same address
Short circuit on cable.
The valve is closed.
Unit is configured but
not present.
Unit is present but not
configured.
There is high current in
the loop cable.
38
Check the cable and the external
load.
Check for obstructions.
Locate the short circuit and fix it.
Locate the short circuit and fix it.
Locate the short circuit and fix it.
Locate the cable break and mend it.
Locate the cable break and mend it.
Check the loop unit addresses
Exchange the unit.
Locate interference and deal with it.
Check the specification and change
definition or the unit.
Exchange the unit
Install the correct type and restart
the loop.
Check the unit.
Change one of the addresses.
Locate the short circuit and fix it.
Open the valve
Add the unit or change the system
configuration.
Remove the unit or change the
system configuration.
Check if there is to many units
connected to the loop. Compare
with the loop limitations.