Download Configuration File From The Salwico Memory Stick Tm; Salwico Cs4000 - Consilium Salwico CS4000 Service Maintenance Manual

Fire alarm system
Hide thumbs Also See for Salwico CS4000:
Table of Contents

Advertisement

Service & Maintenance manual

Salwico CS4000

Chapter 6: Software
Download configuration file from the Salwico
TM
Memory Stick
1. Connect the Salwico Memory Stick
USB ports on the USB expansion board (piggyback
board located on the Base Board).
2. Choose Menu/ 6 Service/ 7 load config from Memory
Stick
3. A list of the available ".c4d" files on the Salwico
Memory Stick
appropriate ".c4d" configuration file from the list and
press OK.
4. The new configuration file is downloaded to the
CS4000.
The old configuration file is automatically renamed
by the system and saved on the Salwico Memory
TM
Stick
.
5. Disconnect the Salwico Memory Stick
6. Use the CS4000 control panel to update the system
with the new configuration file by choosing:
-Menu/ 6 Service menu/ 6 Reload Configuration/
1 Load entire configuration
or
-Menu/ 6 Service menu/ 6 Reload Configuration/
2 Load supplementary texts only
7. If 1 Load entire configuration is selected above, the
Base Board will re-start and load the new
configuration file.
If 2 Load supplementary texts only is selected, the
system will use the new texts without having to re-
start. Any other changes made to the ".c4d" file will
be ignored, but will come into effect the next time the
system is re-started.
TM
will be presented. Choose the
16
TM
to one of the
TM

Hide quick links: