Fujitsu WATERSTAGE 112 Maintenance Document page 76

Waterstage series 3 phase air/water heat pump split system, single service
Hide thumbs Also See for WATERSTAGE 112:
Table of Contents

Advertisement

Heat Pump, Split System, Single Service, 3 phase
Heating curve displacement
The
curve
shift
(offset)
temperature in a general and even manner over the
full range of outdoor temperature. In other words,
the shift should be corrected when the room
temperature is generally too high or too low.
Heating curve adaptation
Adaptation enables the controller to automatically
adapt the heating curve to the present conditions.
This
correction
may
deactivated.
In the latter case, there is no need to correct the
slope and shift.
Eco Functions
Line no.
HC1
HC2
730
1030
732
1032
Summer/winter heating limit
The summer/winter heating limit switches the heating
on or off through the year according to the
temperature
ratio.
automatically when in automatic mode and thus
avoids the user having to turn the heating on or off.
Changing the input value makes the respective
annual periods (summer/winter) shorter or longer.
If the value is increased:
-
Changing to winter operating mode is advanced,
changing to summer mode is delayed
If the value is decreased:
-
Changing to winter mode is delayed; changing to
summer mode is advanced.
Example:
76
modifies
the
only
be
activated
Programming line
Summer/winter heating limit
24-Hour heating limit
Changeover
is
performed
Information:
To ensure operation, the following requirements
must be met:
flow
A room sensor must be connected.
-
The "room influence" parameter must be
-
set between 1 and 99.
The reference room (where the room
-
sensor is installed) must not contain adjusted
thermostatic valves. If present in the room, these
valves must be fully open.
Operation of this function requires an
-
adaptation period which can take more or less time
or
(approx. 1 week) depending on weather conditions
and on the stability of the room temperature
setpoint.
Information:
This function does not work in "Continuous Comfort
temperature" mode. (Sunlight)
The controller displays "ECO".
The outdoor temperature is attenuated to take the
building's dynamics into account.
Attenuated outdoor T
Sum/win heating limit + 1°C
Sum/win heating limit
Sum/win heating limit - 1°C
Days
Maintenance Document 1394-1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Waterstage 140Waterstage 160

Table of Contents