Fujitsu WATERSTAGE 112 Maintenance Document page 47

Waterstage series 3 phase air/water heat pump split system, single service
Hide thumbs Also See for WATERSTAGE 112:
Table of Contents

Advertisement

Heat Pump, Split System, Single Service, 3 phase
Clear 33: Detection of compressor position error (permanent stoppage)
Hydraulic Unit LED: Green 9 flashes / Red 5 flashes
Outdoor Unit LED: 14 flashes
Probable causes:
Misconnection.
Inverter PCB failure.
Check:
1. Check connections condition in control unit:
- Check if the terminal connection is loose.
- Check if connector is removed.
- Check if connector is erroneous connection.
- Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
2. Replace the electronic board :
If steps 1 do not solve the problem, replace Inverter PCB.
-
Maintenance Document 1394-1