Fujitsu WATERSTAGE 112 Maintenance Document page 37

Waterstage series 3 phase air/water heat pump split system, single service
Hide thumbs Also See for WATERSTAGE 112:
Table of Contents

Advertisement

Heat Pump, Split System, Single Service, 3 phase
Clear 14: Expansion valve thermistor error
Hydraulic Unit LED: Green 7 flashes / Red 8 flashes
Outdoor Unit LED: 6 flashes
Probable causes:
Misconnection.
Sensor failure.
Main PCB failure.
Check:
1. Check the sensor connection:
See if the connector has been removed
-
See if the connection is correct
-
Check for any damage on the sensor cable.
-
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature (°C)
Resistance (kΩ)
168 130 101
Temperature (°C)
60
Resistance (kΩ)
12,3 8,7
- If the thermistor is faulty, replace it.
3. Check the electronic board voltage:
- Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
- If there is no voltage, replace Main PCB.
Maintenance Document 1394-1
OK
0
5
10
15
79
70
80
90
100 120
6,3
4,6
3,4
OK
20
30
40
50
63
40
26,3 17,8
2
37