Proof Test Interval; Competence; Residual Risk; Intentional Misuse - ABB ACS880-07 User Manual

Prevention of unexpected start-up (option +q957)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Proof test interval

After the operation of the safety function is validated at start-up, the safety function must
be maintained by periodic proof testing. In high demand mode of operation, the maximum
proof test interval is 20 years. In low demand mode of operation, the maximum proof test
interval is 2 or 5 years (high or low demand as defined in IEC 61508, EN/IEC 62061 and
EN ISO 13849-1). Regardless of the mode of operation, it is a good practice to check the
operation of the safety function at least once a year. Do the test as described in section
Start-up and acceptance test
The person responsible for the design of the complete safety function should also note the
Recommendation of Use CNB/M/11.050 published by the European co-ordination of
Notified Bodies for Machinery concerning dual-channel safety-related systems with
electromechanical outputs:
When the safety integrity requirement for the safety function is SIL 3 or PL e (cat. 3 or
4), the proof test for the function must be performed at least every month.
When the safety integrity requirement for the safety function is SIL 2 (HFT = 1) or PL d
(cat. 3), the proof test for the function must be performed at least every 12 months.
This is a recommendation and depends on the required (not achieved) SIL/PL. For
example, safety relays, contactor relays, emergency stop buttons, switches etc. are
typically safety devices which contain electromechanical outputs. The STO circuit of the
drive does not contain any electromechanical components.

Competence

The maintenance and proof test activities of the safety function must be carried out by a
competent person with adequate expertise and knowledge of the safety function as well as
functional safety, as required by IEC 61508-1 clause 6.

Residual risk

The safety functions are used to reduce the recognized hazardous conditions. In spite of
this, it is not always possible to eliminate all potential hazards. Therefore the warnings for
the residual risks must be given to the operators.

Intentional misuse

The safety circuit is not designed to protect a machine against intentional misuse.

Decommissioning

When you decommission a POUS group or a drive, make sure that the safety of the
machine is maintained until the decommissioning is complete.
on page 16.
Option description and instructions 19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-17Acs880-37

Table of Contents