Operation Principle - ABB ACS880-07 User Manual

Prevention of unexpected start-up (option +q957)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

Operation principle

-T22
-A65
-Sxx
1)
Reset (automatic)
Sxx
POUS switch (user-defined)
Pxx
POUS indication lamp (user-defined)
X969
STO terminal block
The dash-dot (
) line in the figure indicates a user-defined installation.
Initial status: The drive is in operation and the motor is not running.
Step
Operation
1.
The user activates Prevention of unexpected start-up by switching off the POUS switch [Sxx].
2.
The POUS safety relay [A65] de-energizes the XSTO inputs IN1 and IN2 of the drive control board
[A41].
The drive indicates the status. See section
3.
The POUS indication lamp [Pxx] switches on.
4.
The motor coasts to zero speed (if running) and cannot start while STO is active.
5.
Normal operation resumes after the user:
• switches on the POUS switch [Sxx]
• resets the drive (if the STO indication parameter 31.22 has been set so that a fault is generated)
• makes sure that the drive has received the start signal (depends on the configuration, see the
firmware manual).
Control relays
24 V
1)
-Pxx
POUS indications
Option description and instructions 13
Drive control board
-A41
A65
POUS safety relay
A41
Control board (inverter unit)
T22
24 V power supply
on page 18.
XSTO
OUT
SGND
IN1
IN2
-X969
1-2
3-4