UPS Input / output characteristics
Source
Normal AC source
Bypass AC source
Load output
(*): depends on output voltage setting, can be modified by software.
(**): set to +/- 4% by default, (1,2,4,8 are possible values), can be modified by software.
Power supplied as a function of input voltage
P/Pn
100%
70%
250V
320V
Permissible UPS overloads as a function of time
P/Pn
1.5
1.25
1.1
1.02
0.5s
30s
60s
Short-circuit current provided by the UPS in Normal or Batterie mode
EX RT 5
: 110 A for 80 ms.
z
EX RT 7
: 110 A for 80 ms.
z
z
EX RT 11
: 150 A for 80 ms.
EX RT Transformer
Nominal power
Nominal current
Input voltage
Voltage drop
Frequency
Isolation (EN 61558-1-2-4)
Operating temperature
Max. operating rel. humidity
Derating / altitude
Dimensions HxWxD (tower)
Dimensions HxWxD (rack 3U)
Weight
Voltage
320 to 465 Volts AC
187 to 264 Volts AC*
230 Volts AC (200/208/220/240/250 V
are possible values)
U
465V
t
120s
11 kVA
63 A
160-280 Volts AC
7 Volts at nominal load
50/60 Hz (+/-10 %)
3.75 kV / 5 M ohms
From 0° to +40°C
95 %
Pn -10 % > 1000 m
444 x 131 x 635 mm
131 x 444 x 635 mm
86.5 kg
5. Appendices
Frequency
40 to 70 Hz
48 to 52 Hz**
50/60 Hz autoranging
(or frequency converter)
34007724EN/AD - Page 37