Chapter 7 Optional Accessories |CFP2000 Series

7-6 EMC Filter

Following table is the external EMC filter, user can choose corresponding zero phase reactor and suitable
shielded cable length in accord to required noise emission and electromagnetic interference level to have
the best configuration to suppress the electromagnetic interference。
When the application does not consider RE and only needs CE to comply with C2 or C1, there is no need
to install zero phase reactor in input side.
CFP2000 Model
Current
VFD007FP4EA-XXX
VFD015FP4EA-XXX
VFD022FP4EA-XXX
VFD040FP4EA-XXX
12.4A
VFD037FP4EA-XXX
VFD055FP4EA-XXX
VFD075FP4EA-XXX
VFD110FP4EA-XXX
VFD150FP4EA-XXX
VFD185FP4EA-XXX
VFD220FP4EA-XXX
VFD300FP4EA-XXX
VFD370FP4EA-XXX
VFD450FP4EA-XXX
VFD550FP4EA-XXX
110A
VFD750FP4EA-XXX
150A
VFD900FP4EA-XXX
180A
Note 1: To comply with the C1 specifications, an EMC magnetic core needs to be installed on the output side.
Note 2: For frame A~C to comply with EN 61800-3 C1 regulations (when the length of the cable is less than 25m, it
complies with the C1 regulations.), a zero phase reactor has to be installed on the output side, Pass the three
UVW cables through the zero phase reactor. But do not pass the earthing cable and the pig tail of the
insulation through the zero phase reactor.
Note 3: When the length of the cable is longer than 25m, do not install the zero phase reactors listed in the table
below. If the motor cables longer than 25m are connected to a zero phase reactor might cause the
overheating of the iron core inside the zero phase reactor. That will damage the insulation of the cable and
even endanger the life or physical safety of individuals.
Note 4: C2 specifications don't require installing a zero phase reactor.
Input

Zero phase reactor

4.3A
6A
8.1A
RF010FP00A
16A
20A
22A
26A
35A
RF006FP00A
42A
50A
66A
RF002FP00A
80A
91A
-
-
-
-
CE Cable Length
EN61800-3
Carrier
Category
frequency
C2
(Hz)
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦8K
75m
≦10K
75m
≦10K
75m
≦4K
75m
≦4K
7-12
Carrier
Category
frequency
C1
(Hz)
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
N1
25m
≦4K
25m
≦4K
25m
≦4K
25m
≦4K
25m
≦4K
Radiation
Emission
EN61800-3
C2
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass