  • Page 1: Operating Instructions

    Operating Instructions VEGAPULS 65 Profibus PA...
  • Page 2: Table Of Contents

    Setup procedure ..... . . Menu schematic ..... . . VEGAPULS 65 - Profibus PA...
  • Page 3 10.4 Industrial property rights....10.5 Trademark ......VEGAPULS 65 - Profibus PA...
  • Page 4 Contents Supplementary operating instructions manuals Information: VEGAPULS 65 is available in many versions and is thus supplied according to customer order. Depending on the selected version, supplementary operating instructions man- uals also come with the delivery. You will find the supple- mentary operating instructions manuals in chapter "Product...
  • Page 5: About This Document

    This symbol indicates special instructions for Ex applications. List The dot set in front indicates a list with no implied sequence. à Action This arrow indicates a single action. Sequence Numbers set in front indicate successive steps in a procedure. VEGAPULS 65 - Profibus PA...
  • Page 6: For Your Safety

    2.2 Appropriate use VEGAPULS 65 is a sensor for continuous level measurement. Detailed information on the application range of VEGAPULS 65 is available in chapter "Product description".
  • Page 7: Fulfilling Namur Recommendations

    Modifications not expressly approved by VEGA will lead to expiry of the operating licence according to FCC. VEGAPULS 65 is in conformity with part 15 of the FCC regulations. Take note of the respective operating regulations: The instrument must not cause any interfering emissions...
  • Page 8: Safety Instructions For Ex Areas

    VEGAPULS 65 was tested and meets the limit values for a digital instrument of class B, according to part 15 of the FCC regulations. The limit values are for protection against interfering emissions during operation in industrial environ- ment.
  • Page 9: Functional Range Of Approved Instruments

    Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection. The environment man- agement system is certified according to DIN EN ISO 14001. VEGAPULS 65 - Profibus PA...
  • Page 10 For your safety Please help us fulfil this obligation by observing the environ- mental instructions in this manual: Chapter "Storage and transport" Chapter "Disposal" VEGAPULS 65 - Profibus PA...
  • Page 11: Product Description

    - Supplementary instructions manual "Plug connector for continuously measuring sensors" (optional) - Ex-specific "Safety instructions" (with Ex-versions) - if necessary, further certificates VEGAPULS 65 consists of the following components: Components Process fitting with antenna system Housing with electronics, optionally available with plug...
  • Page 12: Principle Of Operation

    Product description Fig. 1: VEGAPULS 65 in threaded version with plastic housing Housing cover with integrated PLICSCOM (optional) Housing with electronics Process fitting with antenna system 3.2 Principle of operation VEGAPULS 65 is a radar sensor in C-band technology Area of application (emitting frequency approx.
  • Page 13: Operation

    (also available as a download).A CD with the appropriate files can be ordered via e-mail under info@de. vega.com or by phone from one of the VEGA agencies under the order number "DRIVER.S". The backlight of the indicating and adjustment module is powered by the sensor.
  • Page 14: Storage And Transport

    PE foil is also used. Dispose of the packaging material via specialised recycling companies. Storage and transport temperature see "Supplement - Storage and transport tem- perature Technical data - Ambient conditions" Relative humidity 20 … 85 % VEGAPULS 65 - Profibus PA...
  • Page 15: Mounting

    Use the recommended cables (see chapter "Connecting to Moisture power supply") and tighten the cable gland. You can give your VEGAPULS 65 additional protection against moisture penetration by leading the connection cable down- ward in front of the cable entry. Rain and condensation water can thus drain off.
  • Page 16: Mounting Instructions

    PTFE washer of the encapsulated antenna system seals. Mount VEGAPULS 65 at least 500 mm (19.685 in) from the Installation position vessel wall. If the sensor is installed in the center of vessels with dished or round tops, multiple echoes can arise.
  • Page 17 In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible down to the lowest point of the vessel bottom. Fig. 5: Vessel with conical bottom VEGAPULS 65 - Profibus PA...
  • Page 18 In case of very big socket diameters, the active antenna part can be slightly recessed in the socket. The following rule applies to the standard version of VEGAPULS 65: Socket diameter corresponds to max. socket height. VEGAPULS 65 - Profibus PA...
  • Page 19 If there are agitators in the vessel, a false echo storage should Agitators be carried out with the agitators in motion. This ensures that the interfering reflections from the agitators are saved with the blades in different positions. VEGAPULS 65 - Profibus PA...
  • Page 20 If foams are causing measurement errors, the biggest possible radar antenna should be used. VEGAFLEX sensors with guided microwaves are not influ- enced by foam generation and are particularly suitable for such applications. VEGAPULS 65 - Profibus PA...
  • Page 21: Connecting To Voltage Supply

    Profibus specification. In particular, make sure that the termination of the bus is done with appropriate terminating resistors. On VEGAPULS 65 with cable gland ½ NPT and plastic Cable gland ½ NPT housing, a metal ½" threaded insert is moulded in the plastic housing.
  • Page 22: Connection Steps Instrument Housing

    5 Insert the cable into the sensor through the cable entry 6 Lift the opening levers of the terminals with a screwdriver (see following illustration) 7 Insert the wire ends into the open terminals according to the wiring plan VEGAPULS 65 - Profibus PA...
  • Page 23: Wiring Plan, Single Chamber Housing

    12 Screw the housing cover back on The electrical connection is finished. 5.3 Wiring plan, single chamber housing The following illustrations apply to the non-Ex as well as to the Ex ia version. VEGAPULS 65 - Profibus PA...
  • Page 24 Fig. 13: Electronics and connection compartment, single chamber housing Plug connector for VEGACONNECT (I²C interface) Spring-loaded terminals for connection of the external indication VEGADIS Ground terminal for connection of the cable screen Spring-loaded terminals for voltage supply VEGAPULS 65 - Profibus PA...
  • Page 25: Wiring Plan, Double Chamber Housing

    Blind stopper or plug M12x1 for VEGADIS 61 (option) Housing cover, electronics compartment Filter element for pressure compensation or blind stopper with version IP 66/ IP 68, 1 bar Cable entry or plug Version IP 66/IP 68, 1 bar not with four-wire instruments VEGAPULS 65 - Profibus PA...
  • Page 26 Terminals for VEGADIS 61 Connection compartment I ² C Fig. 17: Connection compartment, double chamber housing Plug connector for VEGACONNECT (I²C interface) Ground terminal for connection of the cable screen Spring-loaded terminals for voltage supply VEGAPULS 65 - Profibus PA...
  • Page 27: Wiring Plan, Double Chamber Housing Exd

    Blind stopper or plug M12x1 for VEGADIS 61 (option) Housing cover, electronics compartment Filter element for pressure compensation or blind stopper with version IP 66/ IP 68, 1 bar Cable entry or plug Version IP 66/IP 68, 1 bar not with four-wire instruments VEGAPULS 65 - Profibus PA...
  • Page 28 Internal connection cable to the connection compartment Terminals for VEGADIS 61 Connection compartment Fig. 21: Connection compartment, double chamber housing Exd Spring-loaded terminals for power supply and cable screen Ground terminal for connection of the cable screen VEGAPULS 65 - Profibus PA...
  • Page 29: Wiring Plan, Version Ip 66/Ip 68, 1 Bar

    (+) and blue (-) to power supply or to the processing system Screen 5.7 Switch-on phase After VEGAPULS 65 is connected to voltage supply or after Switch-on phase voltage recurrence, the instrument carries out a self-check for approx. 30 seconds. The following steps are carried out: Internal check of the electronics Indication of the instrument type, the firmware as well as...
  • Page 30: Setup With The Indicating And Adjustment Module Plicscom

    (you can choose any one of four different positions - each displaced by 90°) 3 Press the indicating and adjustment module onto the electronics and turn it to the right until it snaps in. VEGAPULS 65 - Profibus PA...
  • Page 31 Fig. 24: Installation of the indicating and adjustment module Note: If you intend to retrofit VEGAPULS 65 with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required.
  • Page 32: Adjustment System

    The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not confirmed with [OK] will not be saved. VEGAPULS 65 - Profibus PA...
  • Page 33: Setup Procedure

    Setup with the indicating and adjustment module PLICSCOM 6.4 Setup procedure After VEGAPULS 65 is connected to voltage supply or after Switch-on phase voltage recurrence, the instrument carries out a self-check for approx. 30 seconds. The following steps are carried out: Internal check of the electronics Indication of the instrument type, the firmware as well as...
  • Page 34 5 Save the settings with [OK] and move to "Max. adjustment" with [->]. Proceed as follows: Carrying out max. adjustment Min. adjustment 100.00 % 1,000 m(d) 2,000 m(d) VEGAPULS 65 - Profibus PA...
  • Page 35 To adapt the sensor to these measuring conditions, this menu item offers different options depending on whether liquid or solid is selected. With "Liquid" these are "Storage tank", "Stilling tube", "Open vessel" or "Stirred vessel", with "Solid", "Silo" or "Bunker". VEGAPULS 65 - Profibus PA...
  • Page 36 [->] key. Caution: Note the following, if VEGAPULS 65 is used as part of an overfill protection system according to WHG: If a linearisation curve is selected, the measuring signal is no longer compulsorily linear proportional to the level.
  • Page 37 The menu item "Extended setting" offers the possibility to Extended setting/Quick level change optimise VEGAPULS 65 for applications in which the level changes very quickly. For this reason, select the function "Quick level change >1m/min.". Extended setting...
  • Page 38 Min. adjustment 35 m(d) (VEGAPULS 62, 66) 70 m(d) (VEGAPULS 68) Medium Liquid Vessel form not known Damping Linearization linear Channel PV lin. % Sensor-TAG Sensor Displayed value PA-Out With standpipe versions. Sensor-specific basic adjustment. VEGAPULS 65 - Profibus PA...
  • Page 39 You will find a detailed description of these menu items in the operating instructions manual "Indicating and adjustment module". Special parameters are parameters which are set customer-specifically on the service level with the adjustment software PACTware™. VEGAPULS 65 - Profibus PA...
  • Page 40: Menu Schematic

    1,000 m(d) 8,000 m(d) 2,000 m(d) Vessel form Linearisation curve Channel Damping ▼ not known linear PV lin. value Sensor-TAG Sensor Indication Basic adjustment ▶ Indication Diagnostics Service Info Displayed value Lighting ▼ PA-Out Switched off VEGAPULS 65 - Profibus PA...
  • Page 41 Info Basic adjustment Indication Diagnostics Service ▶ Info Sensor type Date of manufacture Last change using PC Sensor characteristics VEGAPULS 6x 15. Dec. 2006 Software version Display now? Serial number 3.32 15. Dec. 2006 12345678 VEGAPULS 65 - Profibus PA...
  • Page 42: Saving The Parameter Adjustment Data

    They are hence available for multiple use or service purposes. If VEGAPULS 65 is equipped with an indicating and adjust- ment module, the most important data can be read out of the sensor into indicating and adjustment module. The procedure is described in the operating instructions manual "Indicating...
  • Page 43: Setup With Pactware™ And Other Adjustment Programs

    A detailed description is available in the online help of PACTware™ and the VEGA DTMs. Note: Keep in mind that for setup of VEGAPULS 65, DTM-Collection 06/2003 or a newer version must be used. VEGAPULS 65 - Profibus PA...
  • Page 44: Parameter Adjustment With Pdm

    All currently available VEGA DTMs are provided in the DTM Collection on CD and can be obtained from the responsible VEGA agency for a token fee. This CD includes also the up-to- date PACTware™ version. The basic version of this DTM Collection incl.
  • Page 45: Maintenance And Fault Rectification

    Maintenance and fault rectification 8 Maintenance and fault rectification 8.1 Maintenance When used as directed in normal operation, VEGAPULS 65 is completely maintenance free. 8.2 Remove interferences VEGAPULS 65 offers maximum reliability. Nevertheless faults Causes of malfunction can occur during operation. These may be caused by the following, e.g.:...
  • Page 46 E013 Fault messages via the indi- cating/adjustment module no measured value available à sensor in boot phase à sensor does not find an echo, e.g. because of faulty installation or incorrect parameter adjustment VEGAPULS 65 - Profibus PA...
  • Page 47: Exchange Of The Electronics Module

    In Ex applications, only an electronics module with appropriate Ex approval may be used. If there is no electronics module available on site, one can be ordered from the VEGA agency serving you. The order data of the sensor must be downloaded into the new Sensor serial number electronics module.
  • Page 48: Instrument Repair

    Electronics module PS-E.60CP. is suitable for C-band Profibus PA VEGAPULS 65, 66 - Profibus PA: PS-E.60CPX (X = without approvals) PS-E.60CPA (A = approval CA according to product list) PS-E.60CPD (D = approval XM, CM, CI, UX, UF according to VEGA product list) PS-E.60CPG (G = approval CX according to product list)
  • Page 49: Dismounting

    Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see "Technical data" If you cannot dispose of the instrument properly, please contact us about disposal methods or return. VEGAPULS 65 - Profibus PA...
  • Page 50: Supplement

    126 (default setting) Current value 10 mA, ±0.5 mA Integration time (63 % of the input 0 … 999 s, adjustable variable) Step response or adjustment time ≤250 ms (ti: 0 s, 10 … 90 %) VEGAPULS 65 - Profibus PA...
  • Page 51 W/0.155 in Measuring accuracy Resolution, general max. 1 mm (max. 0.039 in) Deviation see diagrams Time to output the correct level (with max. 10 % deviation) after a sudden level change. Incl. non-linearity, hysteresis and non-repeatability. VEGAPULS 65 - Profibus PA...
  • Page 52 Supplement 20 mm 10 mm 1,0 m 30 m -10 mm -20 mm Fig. 27: Accuracy VEGAPULS 65 in mm, measuring range in m 0.788 in 0.394 in 3.280 ft 98.43 ft - 0.394 in - 0.788 in Fig. 28: Accuracy VEGAPULS 65 in Inch, measuring range in ft Influence of the ambient temperature to the sensor electronics...
  • Page 53 - Other process fittings -40 … +150 °C (-40 … +302 °F) Vibration resistance mechanical vibrations with 4 g and 5 … 100 Hz Tested according to the regulations of German Lloyd, GL directive 2 VEGAPULS 65 - Profibus PA...
  • Page 54 - wire resistance <0.036 Ohm/m (0.011 Ohm/ft) - Tensile strength >1200 N (270 lbf) - Standard length 5 m (16.4 ft) Depending on the version M12x1, according to DIN 43650, Harting, Am- phenol-Tuchel, 7/8" FF. VEGAPULS 65 - Profibus PA...
  • Page 55 - EEx ia instrument 12 … 30 V DC Power supply by/max. number of sensors - DP/PA segment coupler max. 32 (max. 10 with Ex) - VEGALOG 571 EP card max. 15 (max. 10 with Ex) VEGAPULS 65 - Profibus PA...
  • Page 56 CI.I-III, Div 1 (IS); CSA CI.I-III, Div 1 (IS)+Cl.I-III, Div 1 Gr.C-G(XP) Ship approvals GL, LRS, ABS, CCS, RINA Others Prerequisite for maintaining the protection is a suitable cable. Deviating data in Ex applications: see separate safety instructions. Depending on order specification. VEGAPULS 65 - Profibus PA...
  • Page 57: Profibus Pa

    GSD file, PNO provides also a general so-called profile-specific GSD file. For VEGAPULS 65 you have to use the general GSD file „PA139700.GSD“. If the general GSD file is used, the sensor must be set to the profile-specific ident number via the DTM software.
  • Page 58 PA-Out Select additional cyclic value Fig. 29: VEGAPULS 65: Block diagram with AI (PA-OUT) value and additional cyclical value TB Transducer Block FB Function Block Module of the PA sensors For the cyclic data traffic, VEGAPULS 65 provides the following modules:...
  • Page 59 The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0). The measured value is transferred as a 32 bit floating point number in the IEEE-754 format. VEGAPULS 65 - Profibus PA...
  • Page 60 (non-cascade) - active advi- Lo-Alarm sory alarm - low limited 0x8a good (non-cascade) - active advi- Hi-Alarm sory alarm - high limited 0x8d good (non-cascade) - active crit- Lo-Lo-Alarm ical alarm - low limited VEGAPULS 65 - Profibus PA...
  • Page 61 Supplement Status Description according to Profi- Possible cause code bus standard 0x8e good (non-cascade) - active crit- Hi-Hi-Alarm ical alarm - high limited VEGAPULS 65 - Profibus PA...
  • Page 62: Dimensions

    ½ NPT Fig. 33: Housing versions in protection IP 66/IP 68, 1 bar (with integrated indicating and adjustment module the housing is 9 mm/0.4 in higher) Stainless steel housing Aluminium double chamber housing Aluminium housing VEGAPULS 65 - Profibus PA...
  • Page 63 ø 33mm ") Fig. 34: VEGAPULS 65, threaded version Thread and hexagon of PVDF for sockets with 50 mm height (inactive length 82 mm, 55/64") Thread and hexagon of PVDF or 316L for sockets with 100 mm height (inactive length 120 mm, 4 23/32") or 250 mm height (inactive length 270 mm, 10 5/8")
  • Page 64 1" " 8xø " 6" 150 lb Fig. 35: VEGAPULS 65, flange version for sockets with 100 mm height (inactive length 120 mm, 4 23/32") or 250 mm height (inactive length 270 mm, 10 5/8") VEGAPULS 65 - Profibus PA...
  • Page 65: Industrial Property Rights

    Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellectuelle. Pour plus d'informations, on pourra se référer au site http://www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad industrial. Para mayor información revise la pagina web http://www.vega.com.
  • Page 66 Supplement VEGAPULS 65 - Profibus PA...
  • Page 67 Supplement VEGAPULS 65 - Profibus PA...
  • Page 68 All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information avail- able at the time of printing. © VEGA Grieshaber KG, Schiltach/Germany 2007 Subject to change without prior notice 28447-EN-070130...