Dip Switch Setting; Troubleshooting; Cover Plates - LEGRAND Wattstopper PW-311 Installation Instructions Manual

Passive infrared 0–10 volt wall switch occupancy sensor
Table of Contents

Advertisement

Available languages

Available languages

Time
Delay
ON
1
2
Mode
Manual - On
Auto - On
Time Delay
Test/3 min
5 minutes
15 minutes
30 minutes
=ON
Default Values Shown
in Bold
Lights do not turn ON with motion (LED does flash)
1. Press and release each button to make sure that the correct lights come ON for each relay. If the lights do NOT turn ON, check wire
connections, especially the Load connection. If the lights turn ON, verify that the correct On Mode is selected with DIP switch 1.
2. Check to see if light level control is enabled: cover the sensor lens with your hand. If the lights come ON, adjust the light level
setting.
3. If lights still do not turn ON, call 800.879.8585 for technical support.
Lights do not turn ON with motion (LED does not flash)
1. Press and release the UP button to make sure that the correct lights come ON. If the lights turn ON, verify that Sensitivity is on
High.
2. Check the wire connections, in particular, the Line connection. Verify that connections are tightly secured.
3. If lights still do not turn ON, call 800.879.8585 for technical support.
Lights do not turn OFF
1. There can be up to a 30 minute time delay after the last motion is detected. To verify proper operation, set switches 2 and 3 to
OFF to start Test Mode. Move out of view of the sensor. The lights should turn OFF in approximately 10 seconds.
2. Verify that the sensor is mounted at least six feet (2 meters) away from any heating/ventilating/air conditioning device that may
cause false detection. Verify that there is no significant heat source (e.g., high wattage light bulb) mounted near the sensor.
3. If the lights still do not turn OFF, call 800.879.8585 for technical support.
Sensing motion outside desired areas
1. Mask the PIR sensor's lens to eliminate unwanted coverage area.
2. Select PIR Sensitivity. See PIR Sensitivity Adjustment and DIP Switch Settings.
Red LED is OFF all the time and the sensor features don't work.
1. Double check the setting for Service Mode to see if it is turned ON. If so, turn it OFF. Also check the setting of the Time Delay
function. See the section on DIP Switch Settings.
2. If the problem still exists, call technical support.
WattStopper PW series wall switches fit behind industry standard decorator-style switch cover plates. Cover plates are not included.
Units come in the following colors, which are indicated by the final suffix of the catalog number (shown here in parentheses):
• White (–W)
• Light Almond (–LA)
DIP SWITCH SETTINGS
Additional
Additional Features
Features
Exit Programming Mode
3
4
5
6
7
8
9
Unused
1
Mode
2 3
Presentation Mode
=OFF

TROUBLESHOOTING

• Gray (–G)
• Black (–B)
6 7
8 9
Visual Alert
Audio Alert
Walk-Thru
PIR Sensitivity
High Trim
Low Trim
Ramp Up Time
Fade Down Time
Light Level Adjust
Power Loss Mode
Service Mode
Preset On Level
Non-Dim Mode
Reset To Default

COVER PLATES

• Ivory (–I)
• Red (–R)
5
Green LED # of Blinks
1=OFF, 2=ON
1=ON, 2=OFF
1=OFF, 2=ON
1=100%, 2=50%
1=10V, 2=Manual Adjustment
1=0V, 2=Manual Adjustment
1=1, 2=2.5, 3=5, 4=10 seconds
1=2.5, 2=5, 3=15, 4=30 seconds
1=Disable, 2=Enable,
3=Smart Light Level
1=Keep Last State,
2=Default On, 3=Default Off
1=ON, 2=OFF
1=OFF, 2=ON
1=Last Non-Zero Value,
2=50%, 3=75%, 4=100%
1=OFF, 2=ON
Press and Hold UP or
DOWN for 5 seconds