No: 29109 – 10/21 rev. 2
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: PW-311
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
PW-311-U is BAA and TAA compliant (Product produced in the U.S.)
The PW Passive Infrared Wall Switch sensors use advanced passive infrared (PIR) technology.
• PW sensors have Multi-Way available on all models.
• A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds following an occupancy
detection.
• The PW-311 has one relay with dimming control capability and two buttons to allow control of the dimming.
• PW sensors contain a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even
if the area is occupied. See the Light Level Adjustment section.
• On loss of normal power to the PW-311, the 0-10V dimming control will open. Any light fed with a separate circuit but controlled by
the unit's 0-10V signal will go to 100%.
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the PW flying leads as shown in the wiring diagram that
is appropriate to the PW model and electrical supply. The ground wire
(green) must be fastened to ground for the sensor to work properly.
3. Attach the sensor to the wall box by inserting screws into the two wide
holes on the top and bottom of the attached metal bracket. Match them up with the
holes in the wall box and tighten. Do not use excessive force when installing the
sensor into the wallbox. Doing so can bend the mounting strap which can affect
button operation.
4. Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF switch
and the lights will turn ON. There is a delay due to initial power-up of the sensor that
only occurs during installation.
5. Test and adjust the sensor if necessary.
6. Install industry standard decorator wall switch cover plate (not included).
WARNING: Grounding the purple and pink wires can damage the unit. Do not apply power
to the sensor until all wires are connected or capped off if the driver is to be installed at a future time.
Signal Wire (Blue with White Stripe) connects to Neutral. For a replacement or retrofit application , it can connect to Ground.
NOTE: : Per UL, the 0-10V negative dimming wire color has been changed from gray to pink.
Wattstopper
Passive Infrared 0–10 Volt Wall Switch Occupancy Sensor (Version 3)
Interrupteur mural 0–10 Volt avec détecteur de mouvement à infrarouges passif (v3)
Sensor de ocupación con interruptor de pared y tecnología de infrarrojo pasivo de
voltaje 0 a 10 (v3)
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltages ......................................................120/240/277 VAC, 50/60 Hz
Load Limits:
@120 VAC ........... 1000-W tungsten ballast, E-ballast, LED, 1/4 HP
@240/277 VAC ............... 1200-W ballast, E-ballast, LED, 1/4 HP
Time Delay Adjustment ..................................................3 to 30 minutes
Walk-Through Mode ....................... 3 minutes if no activity after 30 sec.
Test Mode ............................................. 10 min. with 10-sec. time delay
PIR Adjustment .................................................................... High or Low
Light Level Adjustment .......................................................8fc to 180+fc
Alerts ........................................................Selectable Audible & Visual
Terminal screw torque ............................................ 16 lbf-in (18 kgf-cm)
High Trim .................................................................................. 6 to 10 V
Low Trim ..................................................................................... 0 to 4 V
Ramp Up ....................................................................... 1 to 10 seconds
Fade Down ................................................................. 2.5 to 30 seconds
Signal Wire, Multi-Way Capability
Complementary Listed to "Emergency Lighting Equipment", (UL924)
DESCRIPTION
INSTALLATION
®
SPECIFICATIONS
WARNING: TURN THE POWER OFF AT
THE CIRCUIT BREAKER BEFORE WIRING.
Yellow
Black
Line
Green
Ground
Neutral
0 a 10V
Dimming
Purple
Driver
Pink
or Ballast
Red
Signal
(Blue w/
White
Stripe)

Advertisement

Table of Contents
loading

Summary of Contents for LEGRAND Wattstopper PW-311-U

  • Page 1 Wattstopper ® Passive Infrared 0–10 Volt Wall Switch Occupancy Sensor (Version 3) Interrupteur mural 0–10 Volt avec détecteur de mouvement à infrarouges passif (v3) Sensor de ocupación con interruptor de pared y tecnología de infrarrojo pasivo de No: 29109 – 10/21 rev. 2 voltaje 0 a 10 (v3) Installation Instructions •...
  • Page 2 MULTI-WAY The Multi-Way capability is available on all models. Sensors can Typical Multi-way Wiring (Up to 4 sensors) easily be wired together for convenient control of a common load. When wiring this way, only use 311 series sensors. Multi-Way in Connect 0-10V Line leads to dimming...
  • Page 3: Button Functions

    BUTTON FUNCTIONS Pressing and holding the UP button will ramp the lights up to the maximum value as determined by the High Trim setting. Pressing and holding the DOWN button will dim the lights down to the minimum value as determined by the Low Trim setting. See Additional Programming Features for detail on setting the trim.
  • Page 4 ADDITIONAL PROGRAMMABLE FEATURES DIP Switches 6 through 9 provide access to a number of additional features. Each feature is selected by choosing a unique combination of the DIP switches. Once you select the specific values, the red LED will blink, indicating you are in Setup Mode. While in Setup Mode, the green LED blinks distinctively—once, twice, three times, or four times—to indicate the current value for that feature.
  • Page 5 To enable light level control and set the threshold: 1. Make sure the room is lit appropriately. 2. Set DIP switches 6–9 to the position needed to access this feature (Up, Down, Down, Up). 3. Press and release the UP button, so that the green LED blinks twice, if you are selecting the Standard mode. Press and release the UP button again, so that the green LED blinks three times, if you are selecting Smart Light Level mode.
  • Page 6: Dip Switch Settings

    DIP SWITCH SETTINGS Time Additional Additional Features Green LED # of Blinks Delay Features Exit Programming Mode Visual Alert 1=OFF, 2=ON Audio Alert 1=ON, 2=OFF Walk-Thru 1=OFF, 2=ON Mode PIR Sensitivity 1=100%, 2=50% Unused High Trim 1=10V, 2=Manual Adjustment Low Trim 1=0V, 2=Manual Adjustment Mode Manual - On...
  • Page 7: Instructions En Français

    INSTRUCTIONS EN FRANÇAIS DESCRIPTION DE L’APPAREIL CARACTÉRISTIQUES TECHNIQUES Les interrupteurs muraux avec détecteur de mouvement à Tensions .............120/240/277 V c.a., 50/60 Hz infrarouge passif PW utilisent technologie de pointe pour Charge nominale : l’infrarouge passif (IRP). à 120 V c.a..ballast tungstène 1 000 W, ballast électronique, DEL, 1/4 HP •...
  • Page 8 MULTI-VOIES Multi-voies câblage standard La fonction de multi-voies est disponible sur tous les modèles. Les (jusqu'à 4 détecteurs) détecteurs peuvent facilement être connectés les uns aux autres pour le contrôle pratique d’une même charge. Si vous effectuez ce type Le raccordement de câblage, utilisez uniquement des détecteurs de la série 311.
  • Page 9: Fonctions Des Boutons

    FONCTIONS DES BOUTONS Le fait de maintenir le bouton HAUT enfoncé permet d’augmenter la lumière jusqu’à la valeur maximale définie à l’aide du paramètre Niveau maximum. Le fait de maintenir le bouton BAS enfoncé permet de réduire la lumière jusqu’à la valeur minimale définie à l’aide du paramètre Niveau minimum.
  • Page 10 MARCHE automatique Lorsque l’interrupteur DIP 1 est placé sur OFF, la charge est ACTIVÉE ou COUPÉE automatiquement en fonction de la présence. Il existe un délai de re-déclenchement de 5 secondes. Si la charge est COUPÉE manuellement, le paramètre activer / désactiver le fonctionnement en mode présentation s’applique.
  • Page 11 NOTE: Le délai d’augmentation lumineuse sera adapté proportionnellement si le niveau de marche préréglé est inférieur à la valeur du niveau maximum. Par exemple, si le niveau minimum est réglé sur 0 V et le niveau maximum sur 10 V (les valeurs par défaut) et que le délai d’augmentation lumineuse est réglé...
  • Page 12: Dépannage

    Rétablir les paramètres d’usine par défaut Maintenez le bouton Haut ou Bas enfoncé pendant 5 secondes. La DEL verte clignote 3 fois pour indiquer que la réinitialisation est terminée. Replacez les interrupteurs DIP 6 à 9 sur OFF. Cette opération réinitialise le détecteur et désactive le contrôle du niveau de luminosité...
  • Page 13 PLAQUES Les interrupteurs muraux de la série PW de WattStopper peuvent être montés derrière des plaques d’interrupteur standard de style Decorator. Les plaques ne sont pas inclus. Les unités sont disponibles dans les couleurs suivantes, indiquées par le suffixe final du numéro de référence (montré ici entre parenthèses): •...
  • Page 14: Instrucciones En Español

    INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN DE LA UNIDAD ESPECIFICACIONES Los sensores con interruptor de pared PW utilizan Voltajes ................. 120/240/277 V CA, 50/60 Hz tecnología infrarroja pasiva (PIR) avanzada. Límites de carga: • Los sensores PW tienen múltiple vías en todos los A 120 V CA .
  • Page 15 MÚLTIPLES VÍAS Cableado típico de múltiples vías La funcionalidad de múltiples vías está disponible en todos los (hasta 4 sensores) modelos. Los sensores pueden cablearse fácilmente en conjunto para un control conveniente de la carga común. Cuando cablee de Conecte los conductores esta manera, solo utilice sensores de la serie 311.
  • Page 16: Funciones Del Botón

    FUNCIONES DEL BOTÓN Al presionar y mantener el botón Arriba se aumentarán las luces al máximo nivel según lo determinado por el ajuste de corte alto. Al presionar y mantener el botón Abajo se regularán las luces al mínimo nivel según lo determinado por el ajuste de corte bajo. Consulte Funciones de programas adicionales para obtener detalles de ajuste del corte.
  • Page 17 Encendido automático Con el conmutador selector para bascular 1 en la posición de Apagado, la carga se enciende y se apaga automáticamente según la ocupación. Hay una demora de 5 segundos de reinicio. Si la carga se apaga manualmente, se aplica la operación del ajuste activar/ desactivar en modo de presentación.
  • Page 18 NOTE: El tiempo de aumento tendrá la escala correcta si el nivel de encendido predeterminado es menor a la cantidad de corte alto. Por ejemplo, si el corte bajo está configurado en 0V y el corte alto está configurado en 10V (los valores predeterminados) y el tiempo de aumento está...
  • Page 19: Solución De Problemas

    Restablecer el valor predeterminado de fábrica Presione y mantenga presionado el botón Arriba o Abajo durante 5 segundos. El LED verde titilará 3 veces para indicar que el restablecimiento está completo. Vuelva los conmutadores selectores para bascular 6 a 9 al estado de apagado. Esto vuelve a configurar el sensor y deshabilita el control de nivel de luz (la luz ambiente más brillante no mantendrá...
  • Page 20 No. 29109 – 10/21 rev. 2 © Copyright 2021 Legrand All Rights Reserved. 800.879.8585 © Copyright 2021 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2021 Legrand Todos los derechos reservados.