DIP SWITCH SETTING

The CI-355 has 7 DIP switches under the cover. They
are used to set time delay and sensor activation LED
settings.
Not Used: Switch 1
Switch 1 has no function. It's position does not affect
the sensor's operation.

Override: Switch 2

To override all sensor functions, set DIP switch 2 to the
ON position. The green LED will come on and stay on
for the duration of the override.
This bypasses the light level and occupancy detection
control functions of the sensor, but still allows the
lights to be manually controlled with a light switch, if
one is installed.
Time Delay: Switches 3, 4, 5
The sensor will hold the lights on as long as occupancy
is detected. The time delay countdown starts when
no motion is detected. After no motion is detected for
the length of the time delay, the sensor will turn the
lights off. The sensor can select the time delay using
SmartSet, or you can select a fixed time delay.
• SmartSet records occupancy patterns and uses this
history to choose an optimal time delay from 5 to 30
minutes. SmartSet behavior starts immediately and
is refined continually as history is collected.
 Walk-through mode turns the lights off three minutes after the area is
initially occupied, if no motion is detected after the first 30 seconds. If motion
continues beyond the first 30 seconds, the selected time delay applies.
LED: Switch 6
When enabled, the green PIR Activity LED under the sensor lens will light when
the sensor detects motion.

Sensitivity: Switch 7

Minimum forces a reduced detection range for the PIR.
Max/SmartSet causes the sensor to monitor the controlled area and automatically
select the maximum sensitivity that will provide reliable operation without false
detection. This setting is constantly updated.
www.wattstopper.com
Feature
Switch
1
Not Used
2
Override
Normal
Override
3 4 5
Time Delay
5 sec/SmartSet
5 minutes
10 minutes
10 minutes
15 minutes
15 minutes
20 minutes
30 minutes
= walk-through mode
6
LEDs
Disabled
Enabled
Sensitivity
7
Minimum
Max/Smartset
= Factory Setting
= ON
-
= OFF

Hide quick links: