2: Required Clearances For Ubbink Concentric Pp, Pvc/Cpvc Snorkel And Tee Terminations - Rinnai RU80i Manual

Twin pipe pvc/cpvc venting guide for condensing tankless water heaters
Hide thumbs Also See for RU80i:
Table of Contents

Advertisement

Additional Clearance Requirements:
Avoid termination locations near a dryer vent.
Avoid termination locations near commercial
cooking exhaust.
Install vent termination at least 12in (304.8mm)
above grade or anticipated snow level.
Vents shall not terminate:
Over public walkways; or near soffit vents or crawl
space vents or other area where condensate or
vapor could create a nuisance or hazard or cause
property damage.
Where condensate or vapor could cause damage
or could be detrimental to the operation of
regulators, relief valves, or other equipment.
Figure 2: Required Clearances for Ubbink Concentric PP, PVC/CPVC Snorkel and Tee Terminations
(1.52 m)
between
terminals at
different levels
V
(0.30 m ) to
an inside
corner
12"
(0.30 m) between
terminals at same
level
INSIDE
CORNER
60"
V
36"
V
V
12"
Important considerations for locating vent
termination under a soffit (ventilated or
unventilated or eave vent; or to a deck or porch):
DO NOT install vent termination under a soffit vent
such that exhaust can enter the soffit vent
Install vent termination such that exhaust and
rising moisture will not collect under eaves.
Discoloration to the exterior of the building could
occur if installed too close.
DO NOT install the vent termination too close
under the soffit where it could present recirculation
of exhaust gases back into the combustion air in-
take part of the termination.
(1.52 m)
V
vertically
between
terminals
60"
V
8
(0.61 m) to wall or parapet
24"
V
12"
(0.30 m) between
terminals at same
V
V
level