NO HARD BYPASS
STEP 6CS
ENABLED
SET
SEPARATE SOURCE
ENABLED
SET
Page 10
Confi guring the Control Valve for Reclamation Mode:
STEP 8CS – Configuring the Control Valve for Water Reclamation Mode - Select Reclaim Enabled for control operation. Motorized Alternat-
Select Reclaim Enabled for control operation. Motorized Alternating Valve will advance to Bypass at a set time after the beginning of
ing Valve will advance to Bypass at a set time after the beginning of regeneration, and return to Service after a set duration. This allows water to
regeneration, and return to Service after a set duration. Up to three bypass events are possible. From the SET screen, pressing SET
be diverted from drain for reuse. Up to three bypass events are possible. Select reclaim enabled for 1 reclaim event, reclaim 2x for two reclaim
CLOCK will increase the number of reclaim cycles up to 3.
events, reclaim 3x for three reclaim events.
The Alternating MAV transitions to Bypass at the set time after the start of regeneration. The start of regeneration is defined as the first cycle that
From the RECLAIM ENABELD screen, pressing the SET CLOCK button will increase the number of reclamation cycles, up to 3. The
is not FILL, SOFTENING or FILTERING. The Alternating MAV will transition back to Service after the completion of the preset duration time.
Alternating MAV transitions to Bypass at a set time after the start of regeneration. The start of regeneration is defi ned as the fi rst cycle
that is not FILL, SOFTENING or FILTERING. The Alternating MAV will transition back to Service after the completion of the preset
duration time.
STEP 8CS
Confi guring the Control Valve to operate with Clack System Controller:
SYSTEM BOARD
Select System Board Enabled to link the Control Valve to the Clack System Controller. For
ENABLED
communication between the Control Valve and the System Controller a three wire communication cable
SET
is required.
Press NEXT to go to Step 5CS. Press REGEN to return to previous step.
AUX MAV OFF
TRIGGER
SET
17
STEP 6CS – No Hard Water Bypass Enabled - Use  or  buttons to select NO HARD WATER BY-
PASS ENABLE. Selection requires that a connection to a Motorized Alternator Valve (MAV) is made to the
two pin-connector labeled MAV DRIVE located on the printed circuit board. The MAV will be driven closed
before the first regeneration cycle that is not FILL or SOFTENING or FILTERING, and be driven open after
the last regeneration cycle that is not FILL. NOTE: If the control valve enters into an error state during
regeneration mode, the no hard water bypass valve will remain in its current state until the error is cor-
rected and reset. Reset by pushing NEXT & REGEN buttons simultaneously until display changes. Press
NEXT to go to Step 10CS.
STEP 7CS – Configuring the Control Valve for Separate Source Operation - Select
STEP 7CS
Separate Source Enabled for control operation. For separate source operation, the three
wire connector is not used. Selection requires that a connection to a MAV is made to the
two pin connector labeled MAV DRIVE located on the printed circuit board. The C port of
the MAV must be connected to the valve inlet and the A port connected to the separate
source used during regeneration. The B port must be connected to the feed water supply.
When set to Separate Source Enabled the MAV will be driven closed before the first regen-
eration cycle, and be driven to open after the last regeneration cycle.
NOTE: If the control valve enters into an error state during regeneration mode, the MAV will
remain in its current state until the error is corrected and reset. Reset by pushing NEXT &
REGEN buttons simultaneously until display changes.
MAV RECLAIM DURATION
STEP 9CS – Configuring the Control Valve to operate with the Hellenbrand System
STEP 9CS
Controller - Select System Board Enabled to link the Control Valve to the SystemMate
Controller. For communication between the Control Valve and the System Controller, a
three-wire communication cable is required.
Press NEXT to go to Step 10CS. Press REGEN to return to previous step.
STEP 10CS – Use the  or  buttons to select one of the following:
STEP 10CS
• Reclaim – Allows brine reclaimation. Select Reclaim for 1 Reclaim Event, Reclaim 2x for
2 reclaim events and Reclaim 3x for 3 reclaim events.
• Separate Source –Allows Auxiliary MAV to switch positions before the start of regenera-
tion and to switch back at the end of regeneration. See instructions in Step 13CS.
• Off - Factory Setting is Off
Press NEXT to go to Step 11CS when reclaim selected as trigger. Press REGEN to return
to previous step.
MAV RECLAIM DURATION
HP Man ual
MAV RECLAIM DURATION

Advertisement