Initial Setting; Address Setting Method; Function Selection Method - Mitsubishi G-50A Installation Manual

Air-conditioner network system central controller
Hide thumbs Also See for G-50A:
Table of Contents

Advertisement

5 Remove the controller's cover and install on to the electric
box.
<Installation on to electric box>
NOTE
* When installing the controller directly on to a wall
instead of using the electric box, do not use the in-
stallation plate.
* If the screw enclosed for the installation plate, fixing
cannot be used because of the wall thickness, pre-
pare an M4 countersunk screw that matches the
wall thickness.
* When using an LAN and external signal I/O, refer to
section 9 External input/output usage method .

6 Initial setting

* Turn on the power supply unit (PAC-SC50KUA) power and run and initially
set this unit.When the power is first turned on, the startup screen shown at
the right is displayed.
(When changing the initially set contents after various initial settings were
performed and the system was already started, the initial setting menu
screen is displayed by pressing the
2 seconds or longer during user operation menu screen display.)
At the end of various initial settings, return to the user operation menu
screen by pressing the
or longer.
Refer to the attached instruction book section 5.Initial setting for further
information.

1. Address setting method

1 When the startup screen is displayed at power on, press the
2 Press the
0
~
9
BACK
3 When the
switch is pressed after setting, the screen returns.
SCREEN
* Always set to [000] when using K transmission converter.
* The M-NET address initial value of this unit is [000].

2. Function selection method

1 On the startup screen, press the
2 Switch the function by pressing the
Each time the switch is pressed, the ON/OFF state of that No. is changed.
No.1 and No.2 cannot be changed.
When Function No. 3 is set to ON, set the K transmission converter address.
Move the address and Function setting using the
<Operation example>
1) When the
switch was pressed
3
BACK
3 When the
switch is pressed, the screen is returned.
SCREEN
<Function Selection Display>
OFF : Not used (Fixed to off)
No. 1
OFF : Not used (Fixed to off)
No. 2
OFF : K transmission converter not provided/ON:K trahsmission converter provided
No. 3
OFF : Operation prohibit transmission valid/ON:Operation prohibit transmission invalid
No. 4
OFF : Emergency stop broadcast enabled/ON: Emergency stop broadcast disabled
No. 5
No. 6
External input changeover
No. 7
The range of a controller which the operation is prohibited.
No. 8
OFF : Both of the systems controller and the local remote controller/ON:Only the local remote controller
and
switches simultaneously for
and
switches simultaneously for 2 seconds
switches, and set the address of this unit. (000,201~250)
2
switch to select "2 FUNCTION SETTING".
1
~
8
ON
OFF
1
switch to select "1 ADDRESS SETTING".
switch of the same No. as the function No. you want to change.
,
,
, and
keys.
3
3
ON
OFF
(OFF)
(ON)
– 5 –
(NOTE)
The cover fixing screw is
packaged with the other enclosed
screws.
Insert a flat-tip screwdriver and
rotate it to remove the cover.
Electric box
Installation plate
M4 countersunk
screw
1 ADDRESS SETTING
2 FUNCTION SETTING
3 IPADDRESS SETTING
4 GROUP SETTING
PLEASE SET