5.5.1. General characteristics of withdrawable circuit-breakers for UniGear ZS1 switchgear

General characteristics of withdrawable circuit-breakers

for UniGear ZS1 switchgear (12 kV)
Circuit-breaker
Standards
VDE 0671; CEI 17-1 (File 1375)
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)(1)
Rated breaking capacity
(rated short-circuit breaking
current symmetrical)
Rated short-time
withstand current (3s)
Making capacity
Operation sequence
[ O - 0.3 s - CO - 15 s - CO ]
Opening time
Arcing time
Total breaking time
Closing time
Maximum
P P
Overall
H
Dimensions
D
Pole distance P [mm]
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility
(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 °C ambient temperature.
(2) 4000 A in UniGear ZS1 switchgear with forced ventilation.
18
VD4/P 12
IEC 62271-100
Ur [kV]
12
Us [kV]
12
Ud (1 min) [kV]
28
Up [kV]
75
fr [Hz]
50-60
Ir [A]
630
1250
Isc [kA]
16
16
20
20
25
25
31.5
31.5
Ik [kA]
16
16
20
20
25
25
31.5
31.5
Ip [kA]
40
40
50
50
63
63
80
80
[ms]
33 ... 60
[ms]
10 ... 15
[ms]
43 ... 75
[ms]
60 ... 80
H [mm]
628
628
W [mm]
503
503
D [mm]
662
662
150
150
116
116
[kg]
TN
7412
7412
1VCD
[°C]
- 5 ... + 40
IEC: 60694
1250
1250
40
40
40
40
100
100
691
691
653
853
641
642
210
275
174
176
3284
3286
1600
1600
20
20
25
25
31.5
31.5
20
20
25
25
31.5
31.5
50
50
63
63
80
80
691
691
653
853
642
642
210
275
160
166
7415
7416