General characteristics of fixed circuit-breakers (17.5 kV)
Circuit-breaker
Standards
VDE 0671; CEI 17-1 (File 1375)
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity
(rated short-circuit breaking
current symmetrical)
Rated short-time
withstand current (3s)
Making capacity
Operation sequence
[ O - 0.3 s - CO - 15 s - CO ]
Opening time
Arcing time
Total breaking time
Closing time
Maximum
P P
Overall
H
Dimensions
Pole distance P [mm]
D
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility
10
VD4 17
IEC 62271-100
Ur [kV]
17.5
Us [kV]
17.5
Ud (1 min) [kV]
38
Up [kV]
95
fr [Hz]
50-60
Ir [A]
630
630
Isc [kA]
16
16
20
20
25
25
31.5
31.5
—
—
Ik [kA]
16
16
20
20
25
25
31.5
31.5
—
—
Ip [kA]
40
40
50
50
63
63
80
80
—
—
[ms]
33 ... 60
[ms]
10 ... 15
[ms]
43 ... 75
[ms]
60 ... 80
H [mm]
461
461
W [mm]
450
570
D [mm]
424
424
150
210
[kg]
73
75
TN
7405
7406
1VCD
—
—
[°C]
- 5 ... + 40
IEC: 60694
630
1250
1250
16
16
16
20
20
20
25
25
25
31.5
31.5
31.5
—
—
—
16
16
16
20
20
20
25
25
25
31.5
31.5
31.5
—
—
—
40
40
40
50
50
50
63
63
63
80
80
80
—
—
—
461
461
461
700
450
570
424
424
424
275
150
210
79
73
75
—
7405
7406
000051
—
—
1250
1250
1250
16
—
—
20
—
—
25
—
—
31.5
—
—
—
40
40
16
—
—
20
—
—
25
—
—
31.5
—
—
—
40
40
40
—
—
50
—
—
63
—
—
80
—
—
—
100
100
461
589
589
700
570
700
424
424
424
275
210
275
79
84
84
—
—
—
000051
003282
003285