General characteristics of withdrawable circuit-breakers for UniGear ZS1 switchgear (24 kV)
Circuit-breaker
Standards
VDE 0671; CEI 17-1 (File 1375)
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
1
Rated normal current (40 °C) (
)
Rated breaking capacity
(rated short-circuit breaking
current symmetrical)
Rated short-time
withstand current (3s)
Making capacity
Operation sequence
[ O - 0.3 s - CO - 15 s - CO ]
Opening time
Arcing time
Total breaking time
Closing time
Maximum
P P
Overall
H
Dimensions
D
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility
(1) Rated current guaranteed with circuit-breaker installed in UniGear ZS1 switchgear and with 40 °C ambient temperature.
(2) 2300 A rated current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
22
VD4/P 24
IEC 62271-100
Ur [kV]
24
Us [kV]
24
Ud (1 min) [kV]
50
Up [kV]
125
fr [Hz]
50-60
Ir [A]
630
Isc [kA]
16
20
25
Ik [kA]
16
20
25
Ip [kA]
40
50
63
[ms]
33 ... 60
[ms]
10 ... 15
[ms]
43 ... 75
[ms]
60 ... 80
H [mm]
794
W [mm]
653
D [mm]
802
Pole distance P [mm]
210
[kg]
140
TN
7413
[°C]
- 5 ... + 40
IEC: 60694
630
1250
1250
16
16
16
20
20
20
25
25
25
16
16
16
20
20
20
25
25
25
40
40
40
50
50
50
63
63
63
794
794
794
853
653
853
802
802
802
275
210
275
148
140
148
7414
7413
7414
1600
2000
2500
16
16
16
20
20
20
25
25
25
16
16
16
20
20
20
25
25
25
40
40
40
50
50
50
63
63
63
838
838
838
853
853
853
790
790
790
275
275
275
228
228
228
7418
7418
7418
(2)