General characteristics of fixed circuit-breakers (24 kV)

Circuit-breaker
Standards
VDE 0671; CEI 17-1 (File 1375)
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
Rated breaking capacity
(rated short-circuit breaking
current symmetrical)
Rated short-time
withstand current (3s)
Making capacity
Operation sequence
[ O - 0.3 s - CO - 15 s - CO ]
Opening time
Arcing time
Total breaking time
Closing time
Maximum
P P
Overall
H
Dimensions
D
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility
12
VD4 24
IEC 62271-100
Ur [kV]
24
Us [kV]
24
Ud (1 min) [kV]
50
Up [kV]
125
fr [Hz]
50-60
Ir [A]
630
Isc [kA]
16
20
25
Ik [kA]
16
20
25
Ip [kA]
40
50
63
[ms]
33 ... 60
[ms]
10 ... 15
[ms]
43 ... 75
[ms]
60 ... 80
H [mm]
631
W [mm]
570
D [mm]
424
Pole distance P [mm]
210
[kg]
100
TN
7409
[°C]
- 5 ... + 40
IEC: 60694
630
1250
1250
16
16
16
20
20
20
25
25
25
16
16
16
20
20
20
25
25
25
40
40
40
50
50
50
63
63
63
631
631
631
700
570
700
424
424
424
275
210
275
104
100
104
7410
7409
7410
1600
2000
2500
16
16
20
20
25
25
25
16
16
20
20
25
25
25
40
40
50
50
63
63
63
642
642
642
700
700
700
424
424
424
275
275
275
110
110
110
7411
7411
7411