General characteristics of withdrawable circuit-breakers for PowerCube modules (24 kV)
Circuit-breaker
Standards
VDE 0671; CEI 17-1 (File 1375)
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated normal current (40 °C)
(1)
Rated breaking capacity
(rated short-circuit breaking
current symmetrical)
Rated short-time
withstand current (3s)
Making capacity
Operation sequence
[ O - 0.3 s - CO - 15 s - CO ]
Opening time
Arcing time
Total breaking time
Closing time
Maximum
P P
Overall
H
Dimensions
D
W
Weight
Standardised table of dimensions
Operating temperature
Tropicalization
IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility
(1) Rated current guaranteed with circuit-breaker installed in PowerCube enclosure and with 40 °C ambient temperature.
(2) 2300 A rated uninterrupted current guaranteed with natural ventilation; 2500 A rated current guaranteed with forced ventilation.
VD4/P 24
Modulo PowerCube
PB4
IEC 62271-100
Ur [kV]
24
Us [kV]
24
Ud (1 min) [kV]
50
Up [kV]
125
fr [Hz]
50-60
Ir [A]
630
Isc [kA]
16
20
25
Ik [kA]
16
20
25
Ip [kA]
40
50
63
[ms]
33 ... 60
[ms]
10 ... 15
[ms]
43 ... 75
[ms]
60 ... 80
H [mm]
794
W [mm]
653
D [mm]
802
Pole distance P [mm]
210
[kg]
140
TN
7413
[°C]
- 5 ... + 40
IEC: 60694
PB4
PB5
1250
1600
16
16
20
20
25
25
16
16
20
20
25
25
40
40
50
50
63
63
794
838
653
853
802
790
210
275
140
228
7413
7418
PB5
PB5
2000
2500
(2)
16
16
20
20
25
25
16
16
20
20
25
25
40
40
50
50
63
63
838
838
853
853
790
790
275
275
228
228
7418
7418
27