Connecting the refrigerant pipe
Refrigerant piping system
Refrigerant piping system table
Max. allowable length
Allowable height length
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter [inch]
1/4
3/8
1/2
5/8
5/8
3/4
7/8
Make sure to use C1220T-1/2H (Semi-hard) pipe for more than 3/4 in. In case of using C1220T-O (Soft) pipe for
3/4 in., pipe may be broken, which can result in an injury.
CAUTION
❋ The appearance of the unit may be different from the diagram depending on the model.
After connecting pipes with knock-out treatment, plug the space.
Following the pipe connection, make sure to proceed precisely to prevent interference with the internal parts.
CAUTION
Actual pipe length
Actual pipe length
Minimum thickness [inch]
0.0276
0.0276
0.0315
0.0394
0.0315
0.0354
0.0354
Make at least one round:
It will reduce noise and vibration
English-18
L0
AC018MXSCCC
L0 + H + L1
98.4 ft (30 m) or less
H
65.6 ft (20 m) or less
L1
H
Pipe length or height
AC024MXSCCC
164.0 ft (50 m) or less
98.4 ft (30 m) or less
Temper grade
C1220T-O
C1220T-1/2H OR C1220T-H