10. Connect the two alarm wires to the specified terminals on the rear side of the replacement
circuit breaker (see
Note: Do not connect any wires to the center terminal on the circuit breaker.
11. Insert the replacement circuit breaker into the opening in the panel and push inward until it
locks into place.
12. Reconnect the power to the power bus.
FRONT VIEW
Figure
19).
LOCKING
TAB
LOCKING
SIDE VIEW
TAB
TO FACILITATE TERMINAL REMOVAL,
USE A NEEDLE-NOSE PLIERS TO GRIP
EACH TERMINAL AT THE POINT SHOWN
Figure 19. Circuit Breaker Wiring Connections
ADCP-80-531 • Issue 4 • July 2004
BREAKER ALARM
NOT USED
LOAD
(WHITE)
CONNECTIONS
POWER
(BLACK)
17339-A