Cable Management Bar (Optional Accessory for Circuit Breaker Panels)

Before installing the circuit breaker panel in the rack, mount the cable management bar (accessory
item, not supplied with panel) on the rear of the panel as shown in
(6.35 mm) long 4-40 screws that are supplied with the cable management bar. The cable
management bar can be recess mounted by using the mounting holes closest to the front of the
panel.
Caution: When attaching the cable management bar to the circuit breaker panel, use only the
hardware supplied with the cable management bar. Use of any other hardware could cause
contact with internal parts of the circuit breaker panel. If parts are missing, please contact ADC.
Note: A circuit breaker panel with the cable management bar attached may exceed the
12-inch (3.05 mm) overall depth objective described in GR-63 CORE, 02-14.
MANAGEMENT
4.5

Rack Mounting

The circuit breaker panel can be mounted in either a 19- or 23-inch (48.26 or 58.42 cm) wide
rack using the 1.75-inch high (4.45 cm), 19- or 23-inch rack mounting brackets. The brackets,
mounting screws, and washers are provided with the panel.
Caution: When attaching the mounting brackets to the circuit breaker panel, use only the
5/16-inch (7.935 mm) long, chromate finish, flathead, thread forming screws supplied with the
panel. Use of any other hardware could cause contact with internal parts of the circuit breaker
panel. If parts are missing, please contact ADC.
Use the following procedure to install the circuit breaker panel in the rack:
1. Attach the mounting brackets to the sides of the chassis using the eight 5/16-inch (7.94
mm) 8-32 flathead thread-forming screws provided. Tighten screws to 15 pound force-
inches (1.7 Newton meters) of torque to insure grounding.
2. Place the fuse panel in the specified mounting space within the rack as shown in
Page 20
© 2006, ADC Telecommunications, Inc.
CABLE
BAR
Figure 11. Cable Management Bar Installation
Figure
11, using the 0.25-inch
MOUNTING BRACKET
INSTALLED FOR
23-IN. (58.42 CM)
RACK MOUNTING
ATTACH TO
EITHER SET
OF 3 HOLES
16759-B
Figure
12.