1.21 Environmental Characteristics

Table 2
lists the environmental characteristics of the PowerWorx Select Series circuit
breaker panel.
Table 2. PowerWorx Select Series Circuit Breaker Panel Environmental Characteristics
PARAMETER
Operating temperature
Storage temperature
Humidity range
Altitude range
Fire rating
Earthquake design
Acoustic noise
Heat dissipation (fully loaded) 50 watts @ 100 Amps per bus, 100 watts @ 200 Amps
Heat dissipation (no load)
19-INCH RACK MOUNTING
BRACKET INSTALLATION
23-INCH RACK MOUNTING
BRACKET INSTALLATION
USE 3/8-INCH (9.525 MM) 12-24
THREAD-FORMING SCREWS AND
WASHERS TO SECURE MOUNTING
BRACKETS TO RACK
Figure 7. Mounting Brackets for Mounting Circuit Breaker Panel
in 19- and 23-Inch (48.26 or 58.42 cm) Racks
DESCRIPTION
–5° C to +55° C
–45° C to +85° C
0% to 95% humidity (non-condensing)
–197 ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level
All components UL94-V1
NEBS Level 3, Zone 4
0 dBA above ambient
total circuit breaker panel load
1 watt per bus
USE 5/16-INCH (7.936 MM) 8-32
THREAD-FORMING FLAT-HEAD
SCREWS TO SECURE MOUNTING
BRACKETS TO PANEL
16965-A
© 2006, ADC Telecommunications, Inc.
ADCP-80-531 • Issue 4 •July 2004