Accessories

Wired Remote docking Kit Accessory

THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM
THE POWER SUPPLY DURING ANY MAINTENANCE AND WHEN FITTING THIS
The Wired Controller Docking Kit is designed so that the Control Module on the MVHR unit can be
mounted remotely. The Docking module is designed to fit a single or double gang flush mounting back
box with a min. depth of 25mm.
The Kit contains the 1 x Docking module, 1 x 15m connection cable, 1 x blank cover and mounting
screws.
Installation.
1. The main printed circuit board following the electrical installation instruction in the Installation &
Commissioning sections of this document.
2.Site the Docking module at a height of 1.5m from the floor and within the distance of a 15m cable
run from the kinetic Advance unit. Do not extend the cable provided.
3. Fit the Connection cable provided into the back box, feed the cable through to the MVHR unit with
the plug in terminal connector end at the back box. Avoid routing cable alongside mains power
cable.
4. To fit the Docking module to the back box, first remove the two screws, one either side.(1) Slide up
the front fascia then press the two tabs at the bottom.(2) This will release the 2 clips that are
retaining the front fascia. You can now slide up the fasica as far as it will go and lift it off the back
section.(3) Fit the cable connector to the socket on the back section. Fit the back section to the
back box by using two screws supplied with the back box.(4) Refit front fascia in reverse order of
its removal.
56
WARNING
CONTROL MODULE.
MVHR Installation and User Guide 476930

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

473881405216474020474025407809407808