Installation

Vertical Discharge Condensate Installation

Note
A water trap with at least a seal of 60mm or a HepVo valve must be fitted between the unit and the
rest of the waste system.
The condensate outlet is compatible with standard 22 mm plastic solvent weld fittings and 32mm plastic
waste pipe fittings.
Wastepipes must have a 3 degree minimum angle to allow the water to drain away from the unit naturally.
In areas where freezing weather conditions occur, outlet pipes must be insulated to avoid blockage by ice,
which may cause damage to the unit and surroundings.
This guide shows a Right Hand configuration for illustration.
If the unit is configured as Left Hand, then the condensate drain should be installed on the left with
the blanking cap on the right.
22mm waste pipe
Solvent weld a small piece of 22mm plastic
waste pipe to the (RH) condensate outlet.
Attach the appropriate pipe fittings for your
installation. Always use a demountable
coupler close to the unit.
Fit a water trap with a seal of at least
60mm, or a HepVo valve close to the unit.
Fit the blanking cap supplied with the unit
to the appropriate side of the unit,
depending on the handing of the unit, see
page 4. Ensure the sealing gasket is fitted
inside the blanking cap.
32mm waste pipe
Attach the appropriate pipe fittings for your
installation to the (RH) condensate outlet.
Fit a water trap with a seal of at least
60mm, or a HepVo valve close to the unit.
Fit the blanking cap supplied with the unit
to the appropriate side of the unit,
depending on the handing of the unit, see
page 4. Ensure the sealing gasket is fitted
inside the blanking cap.
22
MVHR Installation and User Guide 476930