SPECIFICATIONS
Model
Suffix AF:
atmospheric, direct burner ignition
Suffix BF:
atmospheric, intermittent pilot burner ignition
including safety timer
Suffix CF:
fan assisted, direct burner ignition
Suffix DF:
fan assisted, intermittent pilot burner ignition
including safety timer
Suffix PF:
as AF except volatile lock-out
Suffix QF:
s BF except volatile lock-out
Suffix RF:
as CF except volatile lock-out
Suffix TF:
as DF except volatile lock-out
Supply voltage
220 ... 240 Vac, 50/60Hz (-15%,+10%)
Power consumption
4 VA
Humidity
90% RH max. at 40°C
Ambient temperature
-15 ... 60°C
Electrical rating (see also note 17.)
Alarm:
220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6 or max 1 mA
Fan:
220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6
LPG outdoor valve: 220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6
Second main valve: 220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6
Electrical connection
High voltage spark: 2.8 x 0.5 mm spade terminal
Optional:
4 mm round terminal
Flame sensing:
4.8 x 0.8 mm spade terminal or 2.8 x
0.5 mm spade terminal for combined
high voltage spark/flame sensing
PCB connectors:
Molex 3003 series suitable for
Molex 3001 female cable connector
S4565AF, BF, CF, DF, PF, QF, RF, TF
Housing (degree of protection)
See:
accessories for degree of protection page 7..
replacement parts and accessories page 66..
Timing (depending on O.S. number)
Self check time (T
):
c
Waiting time (T
):
w
Safety time (T
):
s
Extended spark ignition time
and stabilisation time:
Flame sensing
Min flame current:
Response time on:
Response time off (T
FR
Ignition
Spark voltage:
Spark energy:
Repetition rate:
Max. spark gap:
Length flame sensing cable
1 m maximum
Length ignition cable
0.5 m max.
Length of wiring for external components
1 m max.
33
1.5 s
0 ... 30 s
3.5 ... 55 s
0 ... T
s
(depending on elaps of safety time)
0.9 µA
> 0.2 s
):
< 1 s
> 12 kV at 40 pF load
(depending on O.S. number)
3 ... 15 µAs
2.5 ... 60 Hz
(depending on O.S. number)
3.5 mm
EN2R-9031 0402R15-NE