SPECIFICATIONS
Model
Suffix A: atmospheric, direct burner ignition
Suffix B: atmospheric, direct burner ignition,
flame relay output
Suffix P: as A except volatile lock-out
Suffix Q
as B except volatile lock-out
Supply voltage
220 ... 240 Vac, 50/60 Hz (-15%, +10%)
Power consumption
4 VA
Humidity
90% RH max. at 40°C non condensing
Storage
- 30 ... 70°C
Ambient temperature
-15 ... 60°C
Electrical rating (see also note 3.)
Alarm:
220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6 or max 1 mA
Flame relay contact: 220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6
Flame opto coupler: +5 V, 10 kΩ
Electrical connection
High voltage spark: 2.8 x 0.5 mm spade terminal
Flame sensing:
4.8 x 0.8 mm spade terminal
PCB connectors:
Molex 3003 series suitable for
Molex 3001 female cable connector
Housing (degree of protection)
See:
accessories for degree of protection page 7..
replacement parts and accessories page 66..
EN2R-9031 0402R15-NE
Timing (depending on O.S. number)
Self check time (T
):
c
Waiting time (T
):
w
Safety time (T
):
s
Extended spark ignition time (T
Flame sensing
Min flame current:
Response time on:
Response time off(T
FR
Ignition
Spark voltage:
Spark energy:
Repetition rate:
Max. spark gap:
Length flame sensing cable
1 m max.
Length ignition cable
0.5 m max.
Length of wiring for external components
1 m max.
Remark
Optional integrated flame relay available with safe separation
or opto coupler with safe separation.
N.C. contact of flame relay has no safe separation.
WARNING
Opto coupler interface needs a
debounce time > 20 ms in order to prevent noise
caused by transients on mains.
10
S4565A, B ,P, Q
1.5 s
0 ...30 s
3.5 ... 55 s
): 0 ... T
max.
x
s
0.9 µA
> 0.2 s
):
< 1 s
(optionally other values available)
>12 kV at 40 pF load
(depending on O.S. number)
3 ... 15 µAs
2.5 ... 60 Hz
(depending on O.S. number)
3.5 mm