Nomenclature and Functions
Indicator
Name
COMM
Communication Yellow
100M
100 Mbps
10M
10 Mbps
Seven-segment Display
16
Color
LED status
Lit
Transferring data
Not lit
Not transferring data
Yellow
Lit
100BASE-TX link established
Not lit
100BASE-TX link not established
Yellow
Lit
10BASE-TX link established
Not lit
10BASE-TX link not established
When the power is turned ON (or the Unit is restarted), the IP address set in
the EtherNet/IP Unit is displayed on the 7-segment display just once, from
right to left. Afterwards, the rightmost 8 bits of the IP address is displayed in
hexadecimal during normal operation.
Example 1: Displaying IP Address 192.168.250.10
The IP address is displayed in decimal, flowing from right to left.
If an error occurs, the error code will be displayed alternately with the right-
most byte of the affected device's IP address. For details on error codes, refer
to ???Section 13 Error Processing and Maintenance.
Displaying Multiple Error Sources
• A d6 error (failed to establish connection) occurred with IP address
192.168.250.8.
• A d6 error (failed to establish connection) occurred with IP address
192.168.250.9.
• A d5 error (verification error, target nonexistent) occurred with IP address
192.168.250.64.
Indicated operating status
If the Unit is operating normally, the last digit of the
Unit's IP address is displayed in hexadecimal.
Flashing: The tag data link is stopped.
Lit: The tag data link is operating.